18 EST iO64 and iO500 Technical Reference Manual
Event ID Event description
023 Reset/Sil inhibit: Reset/silence inhibit is activated
024 Panel silence: The control panel buzzer has been silenced
025 Signal silence: The control panel NACs have been silenced
026 Drill: The control panel is in the drill state
027 Walk test: The control panel is in the walk test state
028 Test fire: A smoke or heat detector is being tested
029 Clear history: The control panel's event history has been
cleared
030 Time: The control panel's time was modified
031 Date: The control panel's date was modified
032 Common disable: A disable event is taking place on the
control panel
033 Common trouble: A trouble event is taking place on the
control panel
034 Ground fault: The panel detected a ground fault
035 Battery charger: The panel detected a battery charger
trouble condition. The charger may not be able to charge
the batteries.
036 Battery low: The batteries are low on charge
037 Battery missing: The battery is no longer connected
038 AC power: There is a problem with the panel's AC power
039 Aux. power 1: The control panel detected a trouble
condition on the continuous AUX power circuit 1
040 Aux. power 2: The control panel detected a trouble
condition on the resettable AUX power circuit 2
041 System AC power: There is a problem with the panel's AC
power and/or a remote auxiliary/booster's AC power
042 Common alarm: An alarm event is taking place on the
control panel
043 Common supervisory: A supervisory event is taking place
on the control panel
044 Common monitor: A monitor event is taking place on the
control panel
045 Common trouble for telco dialer: A trouble event, other
than a DACT delivery fault is taking place on the control
panel
046 Common trouble for network dialer: A trouble event,
including a DACT delivery fault is taking place on the
control panel
047 Self test fault: A fault has been detected while testing the
panel's internal subsystems (memory, flash, code, etc.)