Chapter 3: Programming
EST iO64 and iO500 Technical Reference Manual 149
Panel events programming
Panel events, such as reset, system startup, and battery low have an
event notification setting for contact ID, dialer, NET, and printer,
which controls where the event is sent when it takes place. Each
event has a factory default setting, which can be used with no
additional programming.
Factory default settings
Panel event Printer Dialer NET CID
Aux. power 1 (disable) Yes None No 500
Aux. power 1 (trouble) Yes Acct 1 Yes 312
Aux. power 2 (disable) Yes None No 500
Aux. power 2 (trouble) Yes Acct 1 Yes 312
Battery charger (disable) Yes None No 500
Battery charger (trouble) Yes Acct 1 Yes 309
Battery low (disable) Yes None No 500
Battery low (trouble) Yes Acct 1 Yes 302
Battery missing (disable) Yes None No 500
Battery missing (trouble) Yes Acct 1 Yes 311
Clear history No Acct 1 Yes 621
Common alarm No Acct 1 Yes 110
Common disable No Acct 1 Yes 500
Common monitor No None No 140
Common supervisory No Acct 1 Yes 200
Common trouble No None No 373
Common trouble for network dialer No None Yes 373
Common trouble for telco dialer No Acct 1 No 373
Date No Acct 1 Yes 625
Dialer disable/remote disconnect Yes Acct 1 Yes 551
Dialer line 1 fault (disable) Yes None No 500
Dialer line 1 fault (trouble) Yes Acct 1 Yes 351
Dialer line 2 fault (disable) Yes None No 500
Dialer line 2 fault (trouble) Yes Acct 1 Yes 352
Dialer deliver fail Yes Acct 1 Yes 354
Dialer normal test No Acct 1 No 602
Dialer abnormal test No Acct 1 Yes 608