Appendix A: Panel specifications
EST iO64 and iO500 Technical Reference Manual 203
SA-DACT dialer Phone line type: One or two loop-start lines on a public, switched network
Phone line connector: RJ-31/38X (C31/38X)
Communication formats: Contact ID (SIA DC-05)
Operating current
Standby/Alarm: 41 mA
Max.: 100 mA
FCC registration number: GESAL01BSADACT
Industry Canada Registration number: 3944A-SADACT
Ringer equivalence number: 0.1B
Ground fault impedance 0 to 5 k
Alarm contact Form C N.O. 24 VDC at 1 A (resistive load)
Trouble contact Form C 24 VDC at 1 A (resistive load)
Supervisory contact Form A N.O. 24 VDC at 1 A (resistive load)
Environmental Temperature: 0 to 49°C (32 to 120°F)
Humidity: 0 to 93% RH, noncondensing
Terminal rating All terminals rated for 12 to 18 AWG (0.75 to 2.5 sq. mm)