EasyManua.ls Logo

GE GCX51A - Ohmic Reach; Torque Check

GE GCX51A
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GEI
-
98328
With
the
current
set
at
5
amperes
and
the
voltage
across
studs
17
-
18
oat
120
volts
,
set
the
phase
shifter
so
that
the
phase
-
angle
meter
reads
300
°
(
i
.
e
.
current
lags
the
voltage
on
studs
17
-
18
by
60
°
)
.
Now
reduce
the
voltage
to
2
volts
and
the
current
to
about
2
amperes
.
Gradually
increase
the
current
until
the
MHO
unit
contacts
just
close
.
This
should
occur
between
4.1
-
4.9
amperes
for
the
2.5
Q
mho
,
and
5.1
-
5.9
amperes
for
the
1.0
Q
mho
.
b
.
Ohmic
Reach
With
the
relay
still
connected
as
shown
in
Figure
10
and
the
E
2
taps
in
the
100
%
position
,
set
the
voltage
at
the
value
shown
in
Table
XI
for
the
relay
to
be
checked
.
Increase
the
current
until
the
MHO
unit
contacts
just
close
.
This
should
occur
within
the
limits
shown
in
Table
XI
:
TABLE
XI
Equiv
.
Test
Reach
(
0
-
0
Ohms
)
Pickup
Basic
Min
.
Reach
(
0
-
N
Ohms
)
V
17
-
18
Set
At
Relay
Amps
19.4
-
20.6
7
40
V
Short
Reach
T
14.6
-
15.4
Standard
Reach
275
5
75
V
Note
that
for
the
test
conditions
the
MHO
unit
sees
a
phase
-
to
-
phase
fault
of
twice
the
basic
minimum
reach
.
c
.
Anqle
-
of
-
Maximum
-
Torque
Check
For
the
angle
-
of
-
maximum
-
torque
check
,
the
connections
of
Figure
10
will
still
be
used
with
the
E
2
taps
still
at
100
%
,
and
the
voltage
set
at
the
value
shown
in
Table
XI
for
the
relay
to
be
checked
.
The
pickup
should
then
be
checked
with
the
current
displaced
30
°
from
the
maximum
torque
position
in
both
the
lead
and
lag
direction
.
Set
the
phase
shifter
so
that
the
phase
-
angle
meter
reads
330
°
.
Note
that
while
the
phase
angle
is
being
set
the
current
should
be
at
5
amperes
and
the
voltage
on
studs
17
-
18
should
be
increased
temporarily
to
120
volts
.
With
voltage
again
at
the
value
shown
in
Table
XI
,
increase
the
current
slowly
until
the
MHO
unit
picks
up
.
The
pickup
current
should
be
22
to
24
amperes
for
the
short
-
reach
relay
and
16.5
to
18.2
amperes
for
the
standard
-
reach
relay
.
Now
reset
the
phase
angle
at
270
°
and
again
check
the
current
required
to
pick
up
the
MHO
unit
.
The
pickup
current
should
fall
within
the
same
limits
given
in
the
previous
paragraph
.
Note
that
the
two
angles
used
in
the
previous
check
,
i
.
e
.
,
330
°
and
270
°
,
are
read
30
°
away
from
the
angle
of
maximum
torque
.
An
examination
of
the
MHO
unit
impedance
characteristic
in
Figure
5
shows
that
the
ohmic
reach
of
the
unit
should
be
the
same
at
both
330
°
and
270
°
and
should
be
0.866
times
the
reach
at
the
angle
of
maximum
torque
.
17
Courtesy of NationalSwitchgear.com

Table of Contents

Related product manuals