EasyManua.ls Logo

GE GCX51A - Other Checks and Tests

GE GCX51A
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GE
1
-
98328
First
,
when
checking
the
MHO
unit
at
angles
of
more
than
30
°
off
the
maximum
reach
position
,
the
error
becomes
relatively
large
with
phase
-
angle
error
.
This
is
apparent
from
Figure
13
where
it
is
seen
,
for
example
,
at
the
zero
-
degree
(
0
°
)
position
that
a
two
or
three
degree
(
2
°
or
3
°
)
error
in
phase
angle
will
cause
a
considerable
apparent
error
in
reach
.
Secondly
,
the
effect
of
the
control
spring
should
be
considered
,
since
the
MHO
unit
can
only
have
a
perfectly
circular
characteristic
when
the
control
spring
torque
is
negligible
.
For
any
normal
level
of
polarizing
voltage
,
the
control
spring
may
be
neglected
,
but
in
testing
the
unit
as
indicated
above
it
may
be
necessary
to
reduce
the
test
-
box
autotransformer
tap
setting
to
a
point
where
the
voltage
supplied
to
the
unit
may
be
relatively
low
.
This
reduces
the
torque
level
,
since
the
polarizing
as
well
as
the
restraint
will
be
low
,
with
the
result
being
that
the
control
-
spring
torque
will
no
longer
be
negligible
.
The
result
of
the
control
spring
at
low
polarizing
voltages
is
to
cause
the
reach
of
the
MHO
unit
to
be
somewhat
reduced
.
In
order
to
see
the
effect
of
the
errors
mentioned
above
in
their
true
proportion
,
it
is
suggested
that
the
reach
characteristic
,
determined
by
test
,
be
plotted
on
an
R
-
X
impedance
diagram
as
typified
by
Figure
5
.
It
is
obvious
that
the
apparent
errors
in
reach
,
resulting
from
phase
-
angle
error
at
angles
well
off
the
maximum
reach
position
,
occur
in
a
region
where
the
fault
impedance
vector
will
not
lie
.
As
for
the
error
introduced
by
spring
torque
,
it
should
be
noted
that
the
MHO
unit
is
not
the
measuring
unit
for
the
primary
protection
but
rather
is
only
a
directional
unit
.
Therefore
,
its
directional
response
is
the
most
important
consideration
.
For
third
-
zone
backup
protection
,
the
MHO
unit
is
the
measuring
unit
,
but
for
remote
faults
the
voltage
at
the
relay
is
not
apt
to
be
low
,
and
furthermore
the
accuracy
of
a
third
-
zone
backup
unit
is
not
as
important
as
that
of
a
first
-
zone
unit
.
In
addition
to
the
above
tests
on
the
MHO
unit
,
it
may
also
be
checked
for
directional
action
with
the
test
-
box
circuit
as
shown
in
Figure
12
.
The
fault
resistor
,
R
,
may
be
zero
,
the
test
reactor
should
be
set
on
the
0.5
ohm
tap
.
With
the
test
-
box
switch
closed
,
the
MHO
unit
contact
should
remain
closed
for
a
current
range
of
6
-
60
amperes
with
2
%
rated
voltage
applied
.
A
voltmeter
should
be
used
to
read
the
voltage
at
studs
17
-
18
of
the
relay
.
The
voltage
over
the
6
-
60
ampere
-
current
range
is
adjustable
by
means
of
the
test
-
box
autotransformer
tap
switches
.
When
the
connections
are
changed
to
the
reverse
position
,
the
MHO
unit
contacts
should
remain
open
for
the
same
conditions
as
described
above
.
c
.
Other
Checks
and
Tests
In
addition
to
the
calibration
checks
on
the
OHM
and
MHO
units
as
described
above
,
it
is
desirable
to
make
the
following
general
tests
:
Check
that
the
voltage
-
selection
link
for
the
OX
transfer
unit
is
in
the
correct
position
for
the
DC
voltage
to
be
used
(
48
,
125
,
or
250
V
)
.
Check
that
the
OX
unit
is
picking
up
at
80
%
of
nominal
rated
voltage
,
as
determined
by
the
link
position
,
by
applying
a
variable
DC
voltage
between
studs
12
and
13
.
1
.
This
can
be
Check
that
the
target
seal
-
in
unit
is
operating
at
tap
value
,
checked
by
means
of
the
connections
in
Figure
12
if
the
zone
-
1
signal
circuit
is
loaded
with
the
proper
by
-
pass
resistor
to
draw
a
current
of
approximately
tap
value
and
the
OHM
and
MHO
contacts
(
and
OC
unit
if
present
)
are
closed
by
hand
.
Be
sure
the
seal
-
in
unit
tap
screw
is
left
in
the
required
position
(
0.6
or
2.0
amps
)
for
the
application
.
2
.
If
it
is
24
Courtesy of NationalSwitchgear.com

Table of Contents

Related product manuals