EasyManua.ls Logo

GE GCX51A - Electrical Check; Testing the OHM Unit; Tests

GE GCX51A
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GEI
-
98328
Electrical
Check
Tests
on
Induction
Units
The
manner
in
which
reach
settings
are
made
for
the
OHM
and
MHO
unit
is
briefly
discussed
in
the
CALCULATION
OF
SETTINGS
section
.
Examples
of
calculations
for
typical
settings
are
given
in
that
section
.
It
is
the
purpose
of
the
electrical
tests
in
this
section
to
check
the
OHM
and
MHO
unit
ohmic
pick
up
at
the
settings
that
have
been
made
for
a
particular
line
section
.
To
eliminate
the
errors
that
may
result
from
instrument
inaccuracies
,
and
to
permit
testing
the
OHM
and
MHO
units
from
a
single
-
phase
AC
test
source
,
the
test
circuit
shown
in
schematic
form
in
Fig
.
11
is
recommended
.
In
this
figure
Rs
+
jXs
is
the
source
impedance
,
SF
is
the
fault
switch
,
and
R
|
_
+
jX
|
_
is
the
impedance
of
the
line
section
for
which
the
relay
is
being
tested
.
The
autotransformer
,
TA
,
which
is
across
the
fault
switch
and
line
impedance
,
is
tapped
in
10
%
and
1
%
steps
so
that
the
line
impedance
R
|
_
+
jX
|
_
may
be
made
to
appear
to
the
relay
very
nearly
as
the
actual
line
on
which
the
relay
is
to
be
used
.
This
is
necessary
since
it
is
not
feasible
to
provide
the
portable
test
reactor
X
|
_
and
the
test
resistor
with
enough
taps
so
that
the
combination
may
be
made
to
match
any
line
.
For
convenience
in
field
testing
,
the
fault
switch
and
tapped
autotransformer
of
Figure
11
have
been
arranged
in
a
portable
test
box
,
Cat
.
No
.
102
L
201
,
which
is
particularly
adapted
for
testing
directional
and
distance
relays
.
The
box
is
provided
with
terminals
to
which
the
relay
current
and
potential
circuits
as
well
as
the
line
and
source
impedances
may
be
readily
connected
.
For
a
complete
description
of
the
test
box
,
the
user
is
referred
to
GET
-
3474
.
a
.
Testing
the
OHM
Unit
To
check
the
calibration
of
the
OHM
unit
,
it
is
suggested
that
the
portable
test
box
,
Cat
.
No
.
102
L
201
;
portable
test
reactor
,
Cat
.
6054975
;
and
test
resistor
,
Cat
.
6158546
be
arranged
with
Type
XLA
test
plugs
according
to
Figure
12
.
These
connections
of
the
test
box
and
other
equipment
are
similar
to
the
schematic
connections
shown
in
Figure
11
except
that
the
Type
XLA
test
plug
connections
are
now
included
.
Use
of
the
source
impedance
Rs
+
jXs
,
simulating
the
conditions
that
would
be
encountered
in
practice
,
is
necessary
only
if
the
relay
is
to
be
tested
for
overreach
or
contact
coordination
,
tests
which
are
not
normally
considered
necessary
at
the
time
of
installation
or
during
periodic
testing
,
impedance
will
usually
be
necessary
in
the
source
connection
to
limit
current
in
the
fault
circuit
to
a
reasonable
value
,
especially
when
a
short
-
reach
unit
is
to
be
checked
,
and
it
is
suggested
that
a
reactor
of
suitable
value
be
used
for
this
purpose
since
this
will
tend
to
limit
harmonics
in
the
fault
current
.
Since
the
relay
is
to
be
tested
for
the
ohmic
reach
that
it
will
have
when
in
service
,
the
value
of
X
|
_
to
select
will
be
the
portable
test
-
reactor
tap
nearest
above
twice
the
relay
phase
-
to
-
neutral
ohmic
reach
.
Explanation
of
the
twice
factor
is
as
follows
;
The
relay
as
normally
connected
(
Vl
-
2
potential
and
11
-
12
current
)
measures
positive
-
sequence
phase
-
to
-
neutral
reactance
.
For
a
phase
-
to
-
phase
fault
,
the
fault
current
is
forced
by
thephase
-
to
-
phase
voltage
through
the
impedance
of
each
of
the
involved
phases
,
test
circuit
,
the
line
impedance
,
Z
|
_
,
is
in
effect
the
sum
of
the
impedance
of
each
of
the
phase
conductors
and
must
be
so
arranged
in
order
to
be
equivalent
to
the
actual
fault
condition
.
Since
the
impedance
of
each
phase
must
be
used
Some
In
the
20
Courtesy of NationalSwitchgear.com

Table of Contents

Related product manuals