GE GCX51A - Control - Spring Adjustment; OHM Unit Checks; Other Checks and Tests; Torque

GE GCX51A
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GEI
-
98328
OHM
Unit
Checks
a
.
Control
-
Spring
Adjustment
Be
sure
that
the
relay
is
well
leveled
in
its
upright
position
,
contact
should
just
touch
its
backstop
.
The
moving
b
.
Ohmic
Reach
and
Angle
of
Maximum
Torque
Since
the
OHM
unit
is
a
reactance
-
measuring
device
,
its
angle
of
maximum
torque
occurs
at
90
°
,
current
lagging
voltage
.
1
.
To
check
the
ohmic
reach
,
use
the
connections
shown
in
Figure
10
.
Set
the
No
.
1
tap
leads
on
100
%
and
set
the
current
at
10
amperes
.
Set
the
phase
shifter
so
that
the
phase
-
angle
meter
reads
270
°
(
i
.
e
.
current
lags
voltage
by
90
°
)
.
Now
vary
the
voltage
across
studs
17
-
18
until
the
point
is
found
where
the
OHM
unit
contacts
just
close
.
This
pickup
point
will
be
different
for
the
standard
-
and
short
-
reach
forms
of
the
relay
,
and
also
will
depend
upon
the
setting
of
the
basic
ohmic
reach
taps
.
Table
XIV
shows
the
pickup
voltage
point
for
the
intermediate
range
settings
in
the
colum
headed
90
°
.
A
±
3
%
variation
is
permissible
.
2
.
To
check
the
angle
of
maximum
torque
use
the
same
connections
and
settings
as
in
(
1
)
above
except
now
set
the
phase
shifter
so
that
the
phase
angle
meter
reads
315
°
(
i
.
e
.
current
lags
voltage
by
45
°
)
.
Again
vary
the
voltage
across
studs
17
-
18
until
the
point
is
found
where
the
OHM
unit
contacts
just
close
.
These
points
are
listed
in
Table
XII
for
the
standard
-
and
short
-
reach
forms
of
the
relay
in
the
column
headed
45
°
.
A
+
3
%
variation
is
permissible
.
Note
that
the
relays
are
normally
shipped
from
the
factory
with
the
basic
minimum
reach
adjustment
taps
on
the
intermediate
setting
,
that
is
,
0.2
ohms
for
the
short
-
reach
form
and
0.5
ohms
for
the
standard
-
reach
form
.
TABLE
XII
OHM
UNIT
CHECK
POINTS
OPERATING
P
0
INTS
(
V
17
_
18
)
I
LAGS
V
BY
+
Z
-
3
%
BASIC
MIN
REACH
SETTING
NO
.
1
TAP
SET
CURRENT
RELAY
900
450
AT
:
8.4
V
14.1
V
0.2
Ohms
0.5
Ohms
100
%
6
V
Short
Reach
Stand
.
Reach
T
5
A
100
%
10
A
10
V
Other
Checks
and
Tests
In
addition
to
the
tests
on
the
OHM
and
MHO
units
,
it
is
recommended
that
the
following
general
tests
and
checks
be
made
as
a
part
of
the
ACCEPTANCE
TEST
routine
.
OHM
-
Unit
Transfer
Relay
(
0
X
1
a
.
The
OHM
-
unit
transfer
relay
,
identified
as
OX
in
Figure
8
,
is
provided
with
a
voltage
-
selection
link
to
adapt
it
for
application
on
48
,
125
or
250
volt
DC
control
.
position
.
that
the
OX
unit
picks
up
at
80
%
or
less
of
the
nominal
tap
voltage
for
each
link
position
.
The
unit
should
be
checked
for
correct
operation
on
each
link
Apply
a
variable
source
of
DC
voltage
across
studs
12
-
13
and
check
18
Courtesy of NationalSwitchgear.com

Table of Contents