EasyManua.ls Logo

GE GCX51A - Operating Principles; MHO Unit; OHM Unit

GE GCX51A
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GEI
-
98328
OPERATING
PRINCIPLES
MHO
Unit
The
MHO
unit
of
the
Type
GCX
51
relays
is
of
the
four
-
pole
induction
cylinder
construction
(
see
Figure
14
)
with
schematic
connections
as
shown
in
Figure
4
.
The
two
side
poles
,
energized
with
phase
-
to
-
phase
voltage
,
produce
the
polarizing
flux
.
The
flux
in
the
front
pole
,
energized
with
a
percentage
of
the
same
phase
-
to
-
phase
voltage
,
interacts
with
the
polarizing
flux
to
produce
restraint
torque
.
The
flux
in
the
rear
pole
,
energized
with
the
two
line
currents
associated
with
the
same
phase
-
to
-
phase
voltage
,
interacts
with
the
polarizing
flux
to
produce
the
operating
torque
.
The
torque
at
the
balance
point
can
therefore
be
expressed
by
the
following
equation
:
T
=
0
=
El
cos
(
0
-
0
)
-
KE
2
where
:
E
=
The
phase
-
to
-
phase
voltage
(
E
12
)
I
=
The
delta
current
(
Ii
-
I
2
)
0
=
Angle
of
maximum
torque
of
the
unit
0
=
Power
factor
angle
of
fault
impedance
K
=
Design
constant
Dividing
through
by
E
2
and
transposing
,
the
equation
reduces
to
the
following
expression
in
terms
of
impedance
:
1
Y
cos
(
0
-
0
)
=
K
cos
(
0
-
0
)
=
K
Thus
the
unit
will
pick
up
at
a
constant
component
of
admittance
at
a
fixed
angle
,
depending
on
the
angle
of
maximum
torque
.
Hence
the
name
MHO
unit
.
or
Z
OHM
Unit
The
OHM
unit
of
the
GCX
51
relays
is
also
of
the
four
-
pole
induction
cylinder
construction
(
see
Figure
14
)
with
schematic
connections
as
shown
in
Figure
4
.
front
and
back
poles
,
energized
with
delta
current
,
produce
the
polarizing
flux
.
The
side
poles
are
energized
with
a
voltage
equal
to
the
difference
between
the
operating
quantity
,
IZT
and
the
restraint
voltage
,
E
,
where
I
is
the
delta
current
and
ZT
is
the
transfer
impedance
of
the
transactor
.
Torque
on
the
unit
results
from
interaction
between
the
net
flux
in
the
side
and
the
polarizing
flux
in
the
front
and
rear
poles
,
and
at
the
balance
point
can
be
expressed
by
the
following
equation
:
T
=
0
=
Kl
(
IZT
-
E
)
sin
p
The
where
:
E
=
phase
-
to
-
phase
voltage
(
E
^
)
I
=
delta
current
(
Ii
-
I
2
)
Zj
=
transfer
impedance
of
transactor
(
design
constant
)
p
=
angle
between
I
and
(
IZj
-
E
)
K
=
design
constant
6
Courtesy of NationalSwitchgear.com

Table of Contents

Related product manuals