EasyManua.ls Logo

GE GCX51A - MHO Unit; OHM Unit

GE GCX51A
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6
E
1
-
98328
The
primary
purpose
of
the
MHO
unit
in
the
type
-
GCX
51
relays
is
to
provide
the
directional
discrimination
that
is
necessary
since
the
OHM
unit
is
inherently
nondirectional
.
The
MHO
unit
directional
characteristic
is
such
that
it
will
operate
correctly
for
either
forward
or
reverse
faults
at
voltages
down
to
1
%
of
rated
voltage
over
a
current
range
of
5
to
60
amperes
.
A
secondary
purpose
of
the
MHO
unit
is
to
measure
fault
impedance
for
the
third
zone
of
protection
.
At
reduced
voltage
,
the
ohmic
value
at
which
the
MHO
unit
will
operate
may
be
somewhat
lower
than
its
calculated
value
.
This
"
pullback
"
or
reduction
in
reach
is
shown
in
Figure
6
for
the
1.0
ohm
MHO
unit
used
in
the
short
-
reach
relay
,
or
in
Figure
7
for
the
2.5
ohm
MHO
unit
used
in
the
standard
-
reach
relay
.
The
percentage
of
relay
reach
for
a
constant
tap
setting
is
expressed
as
a
function
of
the
three
-
phase
fault
current
,
I
30
,
for
various
ohmic
reach
settings
.
The
MHO
unit
will
operate
for
all
points
to
the
right
of
the
curves
.
The
static
curves
of
Figures
6
and
7
were
determined
by
tests
performed
with
no
voltage
supplied
to
the
relay
before
the
fault
was
applied
.
The
dynamic
curves
were
obtained
with
full
rated
voltage
of
120
volts
supplied
to
the
relay
before
the
fault
was
applied
.
These
dynamic
curves
illustrate
the
effect
of
the
MHO
unit
memory
action
,
which
maintains
the
polarizing
voltage
on
the
unit
for
a
few
cycles
after
the
inception
of
the
fault
.
This
memory
action
is
particularly
effective
at
low
voltage
levels
where
it
enables
the
MHO
unit
to
operate
for
low
fault
currents
.
This
can
be
most
forcefully
illustrated
for
a
zero
-
voltage
fault
by
referring
to
Figure
7
.
A
zero
-
voltage
fault
must
be
right
at
the
relay
bus
and
therefore
,
to
protect
for
this
fault
,
it
is
imperative
that
the
relay
reach
zero
percent
(
0
%
)
of
its
setting
.
Figure
7
shows
that
the
MHO
unit
,
under
static
conditions
,
will
not
see
a
fault
at
zero
percent
(
0
%
)
of
the
relay
setting
regardless
of
the
tap
setting
.
However
,
under
dynamic
conditions
when
the
memory
action
is
effective
,
Figure
7
shows
that
a
2.5
-
ohm
MHO
unit
with
a
100
%
tap
setting
will
pick
up
if
I
30
is
greater
than
2.5
A
.
This
is
of
course
a
marginal
condition
.
The
minimum
fault
currents
considered
safe
are
listed
in
Table
I
in
the
APPLICATION
section
.
OHM
Unit
The
OHM
unit
impedance
characteristic
when
represented
on
the
R
-
X
diagram
(
Figure
5
)
is
a
straight
line
parallel
with
the
R
axis
.
The
unit
will
operate
for
fault
impedances
lying
below
its
characteristic
,
and
hence
is
non
-
directional
.
During
normal
conditions
when
load
is
being
transmitted
over
the
protected
line
,
the
voltage
and
current
supplied
to
the
unit
present
an
impedance
that
lies
close
to
the
R
axis
since
load
will
be
very
near
unity
power
factor
in
contrast
with
the
reactive
KVA
that
flows
during
fault
conditions
.
An
impedance
near
the
R
axis
will
lie
below
the
OHM
unit
characteristic
(
see
Figure
5
)
and
hence
the
OHM
unit
contact
will
be
closed
.
This
will
cause
no
trouble
,
however
,
since
the
directional
MHO
unit
contact
will
not
be
closed
for
this
condition
(
see
Figure
3
)
.
The
basic
minimum
reach
of
the
OHM
unit
as
listed
in
Table
II
under
RATINGS
is
obtained
when
the
restraint
tap
leads
are
on
100
%
.
The
ohmic
reach
can
be
extended
by
setting
the
restraint
tap
leads
on
a
lower
percentage
position
on
the
tap
block
.
The
setting
of
the
two
tap
leads
marked
No
.
1
determines
the
reach
of
the
instantaneous
or
first
zone
,
and
the
setting
of
the
two
tap
leads
marked
No
.
2
determines
the
reach
of
the
intermediate
or
second
zone
.
8
Courtesy of NationalSwitchgear.com

Table of Contents

Related product manuals