GE GCX51A - Target; Seal - in Unit; Installation Procedure; Connections; Location

GE GCX51A
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GEI
-
98328
b
.
Target
/
Seal
-
in
Unit
The
target
/
seal
-
in
unit
has
an
operating
coil
tapped
at
0.6
or
2.0
amperes
.
The
relay
is
shipped
from
the
factory
with
the
tap
screw
in
the
0.6
ampere
position
.
The
operating
point
of
the
seal
-
in
unit
can
be
checked
by
connecting
from
a
DC
source
(
+
)
to
stud
11
of
the
relay
and
from
stud
3
through
an
adjustable
resistor
and
ammeter
back
to
(
-
)
.
Connect
a
jumper
from
stud
15
to
stud
3
also
,
so
that
the
seal
-
in
contact
will
protect
the
MHO
unit
contact
.
Then
close
the
MHO
contact
by
hand
and
increase
the
DC
current
until
the
seal
-
in
unit
operates
.
It
should
pick
up
at
tap
value
or
slightly
lower
.
Do
not
attempt
to
interrupt
the
DC
current
by
means
of
the
MHO
contact
.
Instead
,
open
the
circuit
externally
or
turn
off
the
DC
source
.
If
it
is
necessary
to
change
the
tap
setting
,
say
from
0.6
to
2.0
amps
,
proceed
as
follows
:
Remove
the
tap
screw
from
the
left
-
hand
contact
strip
and
insert
it
in
the
2.0
amp
position
of
the
right
-
hand
contact
strip
.
Then
remove
the
screw
from
the
0.6
amp
tap
and
put
it
in
the
vacant
position
in
the
left
-
hand
plate
.
If
this
procedure
is
followed
the
contact
adjustments
will
not
be
disturbed
.
INSTALLATION
PROCEDURE
Location
The
location
of
the
relay
should
be
clean
and
dry
,
free
from
dust
,
excessive
heat
and
vibration
,
and
should
be
well
lighted
to
facilitate
inspection
and
testing
.
Mounting
The
outline
and
panel
-
The
relay
should
be
mounted
on
a
vertical
surface
,
drilling
dimensions
are
shown
in
Figure
32
.
Connections
The
internal
connections
of
the
GCX
51
A
and
B
relays
are
shown
in
Figure
8
.
An
elementary
diagram
of
typical
external
connections
is
shown
in
Figure
3
.
It
will
be
noted
in
Figure
8
that
as
shipped
from
the
factory
,
internal
jumpers
are
connected
between
cradle
terminals
17
-
19
and
18
-
20
.
If
it
is
desired
to
use
a
separate
polarizing
potential
,
these
internal
jumpers
can
be
removed
.
The
restraint
voltage
would
then
be
connected
to
studs
17
-
19
and
the
polarizing
voltage
to
19
-
20
.
Visual
Inspection
Remove
the
relay
from
its
case
and
check
that
there
are
no
broken
or
cracked
component
parts
and
that
all
screws
are
tight
.
Mechanical
Inspection
Recheck
the
seven
adjustments
mentioned
under
Mechanical
Inspection
in
the
section
on
ACCEPTANCE
TESTS
.
19
Courtesy of NationalSwitchgear.com