EasyManua.ls Logo

GE GCX51A - Operating Time

GE GCX51A
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GEI
-
98328
The
tap
setting
required
to
protect
a
zone
X
ohms
long
,
where
X
is
the
positive
-
phase
-
sequence
reactance
(
phase
-
to
-
neutral
)
expressed
in
secondary
ohms
,
is
determined
by
the
following
equation
:
Output
Tap
Setting
(
%
)
=
f
Input
Tap
Setting
(
%
)
}
fBasic
Min
.
Ohms
)
X
For
a
numerical
example
of
the
determination
of
the
OHM
and
MHO
unit
settings
,
refer
to
the
section
on
CALCULATIONS
OF
SETTINGS
.
The
purpose
of
the
OHM
unit
in
the
GCX
51
relays
is
to
provide
an
accurate
measurement
of
the
distance
to
a
fault
and
to
close
its
contacts
if
the
fault
lies
within
the
first
or
second
zone
protected
by
the
relay
.
The
overreach
of
the
OHM
unit
from
transient
offset
of
the
fault
current
is
very
small
,
even
with
highly
lagging
line
impedances
,
and
can
be
neglected
for
relay
settings
within
the
recommended
ranges
.
Operating
Time
The
operating
time
of
the
Type
GCX
51
relay
is
determined
by
a
number
of
factors
such
as
basic
minimum
reach
of
the
OHM
and
MHO
units
,
fault
-
current
magnitude
,
ratio
of
fault
impedance
to
relay
reach
,
and
whether
relay
voltage
prior
to
the
fault
is
at
rated
120
volts
or
is
zero
(
0
)
.
A
series
of
figures
is
included
at
the
rear
of
the
book
showing
operating
time
of
the
MHO
unit
and
overall
operating
time
of
the
relay
for
a
number
of
typical
conditions
.
The
operating
time
of
the
MHO
unit
is
given
separately
because
this
unit
is
frequently
used
for
the
carrier
-
stop
function
in
directional
comparison
carrier
schemes
.
The
time
-
curve
figures
are
listed
in
Table
IV
for
the
MHO
unit
alone
and
in
Table
V
for
the
relay
.
TABLE
IV
Time
Curves
for
MHO
Unit
Alone
Volts
Prior
to
Fault
Basic
Min
.
Reach
(
MHO
Unit
)
Figure
#
Relay
lb
120
1.0
ohm
Short
Reach
Stand
.
Reach
0
16
1.0
ohm
17
120
2.5
ohm
18
0
2.5
ohm
In
each
figure
it
will
be
noted
that
time
curves
are
given
for
three
ratios
of
fault
impedance
to
relay
reach
setting
.
In
the
case
of
the
figures
for
the
zero
-
voltage
condition
,
an
additional
curve
(
shown
dotted
)
is
also
given
for
a
4
-
volt
resistive
fault
condition
.
In
all
cases
,
the
E
?
and
/
or
the
No
.
1
taps
were
in
the
100
%
position
and
the
MHO
unit
angle
of
maximum
torque
was
set
at
60
°
lag
.
9
Courtesy of NationalSwitchgear.com

Table of Contents

Related product manuals