EasyManua.ls Logo

GE GCX51A - Page 22

GE GCX51A
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GE
1
-
98328
percent
tap
setting
for
pickup
is
determined
.
This
difference
results
from
the
fact
that
,
unlike
the
OHM
unit
,
the
impedance
pickup
characteristic
of
the
MHO
unit
on
an
R
-
X
diagram
is
a
circle
passing
through
the
origin
.
The
diameter
of
this
circle
is
the
reach
of
the
unit
at
its
angle
of
maximum
torque
,
which
is
normally
60
°
with
respect
to
the
R
axis
.
Since
the
reactance
of
the
test
reactor
may
be
very
accurately
determined
from
its
calibration
curve
,
it
is
desirable
to
check
relay
pickup
with
the
fault
reactor
alone
,
due
account
being
taken
of
the
angular
difference
between
the
line
reactance
,
X
[
_
,
and
relay
angle
of
maximum
reach
.
As
in
the
case
of
the
OHM
unit
,
the
line
reactance
selected
,
X
(
_
,
should
be
the
test
reactor
tap
nearest
above
twice
the
MHO
unit
reach
,
with
account
being
taken
of
the
difference
in
angle
of
the
test
reactor
tap
impedance
and
the
relay
angle
of
maximum
reach
.
From
Figure
13
it
is
seen
that
twice
the
relay
reach
at
the
angle
of
the
test
reactor
impedance
is
:
2
ZRelay
=
2
E
^
m
|
n
cos
(
p
-
e
)
where
:
0
=
angle
of
test
reactor
impedance
9
=
MHO
unit
angle
of
maximum
reach
The
test
-
box
autotransformer
percent
tap
for
MHO
unit
pickup
is
then
given
by
the
equation
:
2
ZRelay
(
100
)
%
Tap
=
ZL
As
an
illustration
of
the
above
,
the
example
in
the
section
on
CALCULATION
OF
RELAY
SETTINGS
will
again
be
used
.
In
this
example
the
E
2
tap
setting
was
calculated
to
be
86
%
,
and
since
a
standard
reach
relay
was
used
the
basic
minimum
reach
of
the
MHO
unit
is
2.5
ohms
at
the
60
°
angle
of
maximum
torque
.
In
determining
the
test
reactor
tap
setting
to
use
,
it
can
be
assumed
as
an
approximation
that
the
angle
0
of
the
test
reactor
impedance
is
80
°
.
Based
on
this
assumption
,
twice
the
relay
reach
at
the
angle
of
the
test
reactor
will
be
:
2.5
x
100
2
ZRelay
=
2
cos
(
80
-
60
)
=
5.6
ohms
86
Twice
the
relay
Therefore
the
6
ohm
tap
of
the
test
reactor
should
be
used
,
reach
at
the
angle
of
test
reactor
impedance
should
be
recalculated
,
using
the
actual
angle
of
the
reactor
tap
impedance
rather
than
the
assumed
80
°
.
XIII
shows
the
angles
for
reach
of
the
reactor
taps
.
Table
TABLE
XIII
COS
4
>
-
60
TAP
ANGLE
m
0.883
0.891
0.899
0.906
0.921
0.934
0.951
24
12
87
86
6
3
85
83
2
81
1
78
0.5
22
Courtesy of NationalSwitchgear.com

Table of Contents

Related product manuals