EasyManua.ls Logo

GE GCX51A - Page 48

GE GCX51A
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GEI
-
98328
APPENDIX
I
In
the
application
of
GCX
51
phase
relays
,
one
relay
is
used
to
provide
phase
fault
protection
for
each
pair
of
phases
.
Thus
one
relay
is
used
for
phases
a
-
b
,
a
second
relay
for
phases
b
-
c
,
and
a
third
relay
for
phases
c
-
a
,
or
a
total
of
three
relays
,
all
of
which
will
operate
for
three
-
phase
faults
within
the
set
reach
.
The
further
limitation
on
the
MHO
unit
reach
,
mentioned
in
the
APPLICATION
and
CALCULATION
OF
SETTINGS
sections
,
is
experienced
on
phase
-
to
-
phase
faults
and
involves
one
of
the
two
relays
associated
with
the
unfaulted
phases
rather
than
the
relay
protecting
the
faulted
phases
.
For
example
,
if
we
assume
a
phase
b
-
c
fault
,
it
is
the
phase
a
-
b
relay
which
may
tend
to
overreach
.
Referring
to
the
R
-
X
diagram
of
Figure
1
-
1
,
OL
represents
the
protected
circuit
with
the
relays
located
at
0
,
and
0
T
represents
the
reach
of
the
first
-
zone
OHM
unit
setting
.
For
a
phase
b
-
c
fault
at
the
first
-
zone
setting
(
T
)
,
the
phase
b
-
c
relay
will
properly
see
an
impedance
0
T
.
However
,
the
phase
a
-
b
relay
will
see
an
impedance
originating
at
0
and
terminating
somewhere
along
the
line
TP
,
depending
on
system
conditions
.
If
this
impedance
happens
to
be
OPi
,
it
will
fall
within
the
first
zone
characteristic
of
the
phase
a
-
b
relay
.
This
is
,
in
effect
,
overreaching
.
If
the
impedance
happens
to
be
0
P
2
,
it
will
fall
outside
the
MHO
characteristic
of
the
a
-
b
relay
and
there
will
be
no
tripping
of
that
relay
.
In
order
to
prevent
the
relay
associated
with
the
unfaulted
phase
from
overreaching
as
described
above
,
it
is
necessary
to
limit
the
reach
setting
of
the
MHO
unit
.
In
order
to
do
this
,
it
is
necessary
to
know
where
along
the
TP
line
the
impedance
seen
by
the
unfaulted
phase
relay
terminates
.
Referring
to
Figure
1
-
1
and
with
everything
plotted
in
terms
of
secondary
ohms
,
the
secondary
impedance
TP
is
equal
to
(
V
3
)
(
ST
)
,
where
ST
is
the
vector
sum
of
the
system
impedance
behind
the
relay
(
OS
)
plus
the
impedance
0
T
,
all
in
secondary
ohms
.
The
system
impedance
is
plotted
as
a
pure
reactance
in
order
to
obtain
conservative
results
.
The
system
impedance
behind
the
relay
in
secondary
ohms
(
Xs
)
may
be
obtained
as
follows
:
Assume
a
three
-
phase
fault
at
the
relay
terminals
of
the
protected
line
and
determine
the
maximum
fault
current
I
'
30
supplied
through
the
relay
terminal
in
secondary
amperes
with
the
remote
breaker
open
.
XS
=
1
30
Once
TP
is
plotted
on
the
R
-
X
diagram
,
a
MHO
circle
may
be
drawn
so
that
the
impedance
,
OP
,
seen
by
the
unfaulted
phase
relays
falls
outside
the
circle
.
In
order
to
simplify
the
investigation
,
the
curves
of
Figure
1
-
2
and
1
-
3
have
been
computed
.
The
family
of
curves
for
various
line
angles
in
Figure
1
-
2
provides
the
means
of
determining
the
permissible
Mho
unit
setting
(
ZMO
)
as
a
multiple
of
the
zone
1
reactance
unit
setting
(
Xou
)
in
terms
of
the
ratio
of
Xs
/
Xou
.
where
Xs
is
the
system
impedance
behind
the
relay
location
.
The
curves
in
Figure
1
-
2
are
on
the
basis
of
no
load
flow
in
the
protected
line
.
Load
flow
into
the
protected
line
at
the
relay
location
tends
to
aggravate
the
situation
represented
by
the
plot
in
Figure
1
-
2
.
In
other
words
,
with
load
present
the
permissible
ratio
of
ZMO
/
XOU
will
be
less
than
the
curves
in
Figure
1
-
2
indicate
.
Then
,
48
Courtesy of NationalSwitchgear.com

Table of Contents

Related product manuals