70
10 Technical Parameters
User Manual V1.0-2023-10-30
Technical Data
GEH15-
3U-10
GEH20-
3U-10
GEH25-
3U-10
GEH29�9-
3U-10
GEH30-
3U-10
Nominal Output Power at 40
℃(W)
*14
15,000 20,000 25,000 29,900 30,000
Max. Output Power at 40 ℃
(W)
*14
15,000 20,000 25,000 29,900 30,000
Nominal Apparent Power
Output to Utility Grid (VA)
15,000 20,000 25,000 29,900 30,000
Max. Apparent Power Output to
Utility Grid (VA)
*3
16,500 22,000 27,500 29,900 33,000
Nominal Apparent Power from
Utility Grid(VA)
15,000 20,000 25,000 30,000 30,000
Max. Apparent Power from
Utility Grid (VA)
*12
15,000 20,000 25,000 30,000 30,000
Nominal Output Voltage (V) 380/400, 3L/N/PE
Output Voltage Range (V)
*4
0~300
Nominal AC Grid Frequency
(Hz)
50/60
AC Grid Frequency Range (Hz) 45~65
Max. AC Current Output to
Utility Grid (A)
*11
23.9 31.9 39.9 43.3 47.8
Max. AC Current From Utility
Grid (A)
*13
21.7 29.0 36.2 43.3 43.5
Nominal AC Current From
Utility Grid (A)
21.7 29.0 36.2 43.3 43.5
Max. Output Fault Current
(Peak and Duration) (A)
241.5A@126ms
Inrush Current (Peak and
Duration) (A)
264A@53us
Nominal Output Current (A)
*5
21.7 29.0 36.2 43.3 43.5
Power Factor ~1 (Adjustable from 0.8 leading~0.8 lagging)
Max. Total Harmonic Distortion <3%
Maximum Output Overcurrent
Protection (A)
94
AC Output Data (Back-up)
Back-up Nominal Apparent
Power (VA)
15,000 20,000 25,000 29,900 30,000