CHAPTER 5: PRODUCT DESCRIPTION SPECIFICATIONS
369 MOTOR MANAGEMENT RELAY – QUICKSTART GUIDE 5–71
ELECTROSTATIC DISCHARGE
EN 61000-4-2, Level 2
IEC 60255-22-2 Level 2
SURGE IMMUNITY
IEC 1000-4-5, EN 61000-4-5
IEC 60255-22-5
CURRENT WITHSTAND
ANSI/IEEE C37.90
IEC 60255-6
RFI
ANSI/IEEE C37.90.2, 35 V/m
EN 61000-4-3 10V/m
CONDUCTED IMMUNITY:.............................IEC 1000-4-6
IEC 60255-22-6
CONDUCTED/RADIATED EMISSIONS
EN 55011 (IEC CISPR 11)
ENVIRONMENTAL
ANSI/IEEE C37.90
IEC 60255-6
IEC 60068-2-38 Part 2
IEC60068-2-1, 16h at -40°C
IEC60068-2-2, 16h at +85°C
IEC60068-2-30, 95% variant 1, 6 days
VIBRATION
IEC 60255-21-1 Class 1
IEC 60255-21-2 Class 1
VOLTAGE DEVIATION
IEC 1000-4-11 / EN 61000-4-11
MAGNETIC FIELD IMMUNITY
IEC 1000-4-8 / EN61000-4-8
5.2.12 Production Tests
DIELECTRIC STRENGTH
All high voltage inputs at 2 kV AC for 1 minute
BURN IN
8 hours at 60°C sampling plan
CALIBRATION AND FUNCTIONALITY
100% hardware functionality tested
100% calibration of all metered quantities