84 GE INFORMATION G500 SUBSTATION GATEWAY INSTRUCTION MANUAL
APPENDIX A: STANDARDS & COMPLIANCE
Relative Humidity Cyclic IEC 60068-2-30
6day, variant 2, 55°C/95%RH
Change of Temperature IEC 60068-2-14
Dual Core:-40°C to 70°C
Quad Core: -40°C to 60°C
Method Nb
Damp Heat Steady State IEC 60068-2-78
40°C & 93%RH for 240 hrs
Damped Oscillatory IEEE/ANSI C37.90.1
2.5kV@1MHz CM/DM
RF Immunity IEEE/ANSI C37.90.2
20V/m 80-1GHz + Spot Freqs
ESD IEEE/ANSI C37.90.3
8kV CD, 15kV AD
IEEE Standard Environmental and
Testing Requirements for
Communications Networking
Devices Installed in Electric Power
Substations
IEEE 1613:2009
Per Standard
Communication Networks and
systems for power Utility
Automation-Part 3
IEC 61850-3:2013
Per Standard
SAFETY EN/IEC 60950-1: 2005
Per standard
UL marking UL60950-1 2
nd
Ed /CSA
C22.2 60950-1-07
NWGQ2 & NWGQ8
TEST REFERENCE STANDARD TEST LEVEL