G500 SUBSTATION GATEWAY INSTRUCTION MANUAL GE INFORMATION 83
G500 Substation Gateway
Appendix A: Standards & Compliance
Standards & Compl iance
Compliance Standards
The G500 complies with the tests listed below. The test methods covered, provide
compliance to IEC61850-3 Location H or G when equipped with a Low voltage power
supply (48Vdc) or High voltage power supply (full nominal range). The G500 is also fully
compliant to IEEE1613: Class 1.
TEST REFERENCE STANDARD TEST LEVEL
Insulation Resistance Test EN 60255-27 500 Vdc
Dielectric voltage withstand EN 60255-27 2.0 kV
Impulse voltage withstand EN 60255-27 5 kV
Damped Oscillatory IEC 61000-4-18 100kHz & 1Mhz 2.5kV CM, 1kV DM
Electrostatic Discharge IEC 61000-4-2 Level 4
RF immunity IEC 61000-4-3 Level 3
Fast Transient Disturbance IEC 61000-4-4 Level 4
Surge Immunity IEC 61000-4-5 Level 3 & 4
Conducted RF Immunity IEC 61000-4-6 Level 3
Radiated & Conducted Emissions CISPR22 & CISPR32 Class A
Sinusoidal Vibration IEC 60255-21-1 Class 1
Shock & Bump IEC 60255-21-2 Class 1
Seismic IEC 60255-21-3 Class 2
Power magnetic Immunity IEC 61000-4-8 Level 5
Voltage Dip & interruption IEC 61000-4-11 0,40,70,80% dips, 250/300cycle interrupts
Conducted RF Immunity 0-150khz IEC 61000-4-16 Level 4
Voltage Ripple IEC 61000-4-17 15% ripple
Ingress Protection IEC 60529 IP30
Environmental (Cold) IEC 60068-2-1 -40°C 16 hrs. (Storage and Operational)
Environmental (Dry heat) IEC 60068-2-2
60°C 16hrs for Quad Core
70°C 16 hrs. Dual Core
85°C 16 hrs. Storage (both models)