EasyManua.ls Logo

GE Multilin G650 - Page 205

GE Multilin G650
639 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5-62 G650 Generator Protection & Control System GEK-113285A
5.4 PROTECTION ELEMENTS 5 SETTINGS
5
Table 5–63: GENERATOR UNBALANCE ELEMENT SETTINGS
• Gen Unbal Function: This setting allows enabling or disabling the element.
• Gen Unbal Inom: This setting is the rated full load current of the machine.
• Gen Unbal Stg1 Pkp: This setting defines the pickup of the stage 1 element expressed as a percentage of the
nominal current as specified by GEN UNBAL INOM setting. It is typically set at the maximum continuous negative
sequence current rating of the machine.
• Gen Unbal Stg1 K: This setting is the negative sequence capability constant. This value is normally provided by the
generator manufacturer.
• Gen Unbal Stg1 Tmin: This is the minimum operate time of the element.
• Gen Unbal Stg1 Tmax: This is the maximum operate time of the element. This setting can be applied to limit the
maximum tripping time.
• Gen Unbal Stg1 K-Rst: This setting defines the linear reset rate of the stage. This feature provides a thermal memory
of previous unbalance conditions.
• Gen Unbal Stg2 Pkp: This setting defines the pickup of the stage 2 element expressed as a percentage of the
nominal current as specified by GEN UNBAL INOM setting.
• Gen Unbal Stg2 Delay: This is the minimum operate time of the stage 2 element.
Table 5–64: GENERATOR UNBALANCE INTERNAL SIGNALS
SETPOINT > PROTECTION ELEMENTS > NEGATIVE SEQUENCE CURRENT > GENERATOR UNBALANCE >
GENERATOR UNBALANCE 1> GENERATOR UNBALANCE 2 > GENERATOR UNBALANCE 3
SETTING DESCRIPTION NAME DEFAULT VALUE STEP RANGE
Function Permision Function DISABLED N/A [DISABLED – ENABLED]
Generator Rated Full Load Current Gen Unbal Inom 5.00 0.01 A [0.00 : 10.00]
Pickup level for stage 1 (as a percentage of
Gen Unbal Inom)
Gen Unbal Stg1 Pkp 8.00 0.01 % [0.00 : 100.00]
K (Negative sequence capability constant) for
stage 1
Gen Unbal Stg1 K 1.00 0.01 [0.00 : 100.00]
Minimum Operating time for stage 1 Gen Unbal Stg1 Tmin 0.3 0.1 s [0.0 : 1000.0]
Maximum Operating time for stage 1 Gen Unbal Stg1 Tmax 600.0 0.1 s [0.0 : 1000.0]
K for Linear reset of the stage Gen Unbal Stg1 K-Rst 240.0 0.1 [0.0 : 1000.0]
Pickup level for stage 2 (as a percentage of
Gen Unbal Inom)
Gen Unbal Stg2 Pkp 3.00 0.01 % [0.00 : 100.00]
Trip time for stage 2 Gen Unbal Stg2 Delay 5.0 0.1s [0.0 : 1000.0]
Snapshot Event generation Snapshot Events ENABLED N/A [DISABLED – ENABLED]
SIGNAL COMMENT
GEN UNBAL (1, 2, 3) BLOCK Input used to block the element (1, 2, 3) externally
GEN UNBAL (1, 2, 3) STG1 PKP Output used to indicate I2/Inom ratio above stage 1 setting
in units (1, 2, 3)
GEN UNBAL (1, 2, 3) STG1 OP Output used to indicate stage 1 operation in units (1, 2, 3)
GEN UNBAL (1, 2, 3) STG2 PKP Output used to indicate I2/Inom ratio above stage 2 setting
in units (1, 2, 3)
GEN UNBAL (1, 2, 3) STG2 OP Output used to indicate stage 2 operation in units (1, 2, 3)
GEN UNBAL1 PKP This status is a logic OR between the GEN UNBAL(1, 2, 3)
STG1 PKP and GEN UNBAL(1, 2, 3) STG2 PKP
GEN UNBAL1 OP This status is a logic OR between the GEN UNBAL(1, 2, 3)
STG1 OP and GEN UNBAL(1, 2, 3) STG2 OP

Table of Contents