GEK-113285A G650 Generator Protection & Control System 5-121
5 SETTINGS 5.6 INPUTS/OUTPUTS
5
5.6.7.2 VIRTUAL INPUTS STATUS MONITORING:
Actual > Inputs/Outputs > Virtual Inputs > Virtual Input Latched > Virtual Input Self-Reset
Table 5–109: VIRTUAL INPUTS STATUS
Text assignment for virtual input is made at Setpoint > Relay Configuration > Virtual Inputs. It should be taken into
account that the text assigned for virtual inputs in the relay configuration screen are only for file management, they are not
sent to the relay.
5.6.8 VIRTUAL OUTPUTS
There are 512 virtual outputs that may be assigned via Logic configuration. If not assigned, the output will be forced to OFF
(Logic 0). An ID may be assigned to each virtual output. Virtual outputs are resolved in each pass through the evaluation of
the logic equations. For more detailed information see chapters 5.8 and 5.9 in this manual.
VIRTUAL INPUTS LATCHED VIRTUAL INPUTS SELF-RESET
LATCHED VIRT IP 1 SELF-RST VIRT IP 1
LATCHED VIRT IP 2 SELF-RST VIRT IP 2
……
LATCHED VIRT IP 32 SELF-RST VIRT IP 32