2-26 G650 Generator Protection & Control System GEK-113285A
2.4 TECHNICAL SPECIFICATIONS 2 PRODUCT DESCRIPTION
2
2.4.5.7 WAR-HOURS (POSITIVE AND NEGATIVE)
2.4.5.8 POWER FACTOR
2.4.5.9 FREQUENCY
Metering range from 30 Hz to 80 Hz
2.4.5.10 ANGLE
2.4.6 INPUTS
2.4.6.1 AC CURRENT INPUTS
Accuracy:
±1.0% of the reading
Range:
±0 to 2147 MVArh
Parameters: 3-phase only
Update rate: 100 ms
Accuracy: 0.02
Parameters: 3-Phase and single phase
Accuracy: ±30 mHz at 50 Hz
±36 mHz at 60 Hz
Accuracy: ±3º
CT Ratio: 1.0 to 6000.0 in steps of 0.1
Rated currents: Appropriate for 1 or 5 A. G650 has universal range for CT (valid for 1 or 5 A to
only one terminal).
Relay Burden: < 0.04 Ohm
Current Withstand Continuous at 20 A
1 second at 500 A for phases and ground
1 second at 50 A for sensitive ground