2-18 G650 Generator Protection & Control System GEK-113285A
2.4 TECHNICAL SPECIFICATIONS 2 PRODUCT DESCRIPTION
2
2.4.2.4 PULSE COUNTERS
2.4.2.5 ANALOG COMPARATORS
Level Accuracy
±0.5% of the reading ± 10 mA from 0.05 to 10 A
±1.5% of the reading for higher values.
Timing accuracy ±3.5% of operate time or 50 ms. (whichever is greater)
Snapshot Events Selectable by setting
Number of Pulse counters available Up to 8
Multiplier factor 0.000 to 65000.000 in steps of 0.001
Overload factor 0 to 1000000 in steps of 1
Board Origin All available input/outputs boards in the device. See
ordering code [F, G, H, J]
Input origin up to 32 [depending on the board type selection]
Analog Input Any analog value available in the device
Analog Maximum Threshold value -100000.000 to 100000.000 in steps of 0.001
Analog Minimum Threshold value -100000.000 to 100000.000 in steps of 0.001
Analog Delay 0.00 to 900.00 in steps of 0.01
Analog Hysteresis 0.0 to 50.00 in steps of 0.1
Analog Direction (for activation inside or outside the
deadband)
IN or OUT