GEK-113285A G650 Generator Protection & Control System 2-21
2 PRODUCT DESCRIPTION 2.4 TECHNICAL SPECIFICATIONS
2
2.4.2.10 BREAKER SETTINGS
Number of Switchgear 1 to 16 (selection of switchgear for breaker control)
Maximum KI
2
t 0.00 to 9999.99 in steps of 0.01 (kA)
2
s
KI
2
t integration Time
0.03 to 0.25 s in steps of 0.01 s
Maximum openings 0 to 9999 in steps of 1
Maximum Openings in one hour 1 to 60 in steps of 1
Snapshot Events Selectable by setting