EasyManua.ls Logo

GE Multilin G650 - Page 554

GE Multilin G650
639 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GEK-113285A G650 Generator Protection & Control System B-127
APPENDIX B B.7 MEMORY MAP
B
Ajustes Derivada de Frecuencia 3-Frequency Rate of Change 3 Settings
0x4170 Function F012 1,000 R/W 1 0=DISABLED
1=ENABLED
0x4171 Freq. Rate Trend F012 1,000 R/W 1 0=INCREASING
1=DECREASING
2=BI-DIRECTIONAL
0x4172 Freq. Rate Pickup F003 1,000 R/W 2 [0.10 , 10.00] Hz/s
0x4174 Freq. Rate OV Supv F003 1,000 R/W 2 [0.00 , 110.00] %
0x4176 Freq. Rate Min F003 1,000 R/W 2 [20.00 , 80.00] Hz
0x4178 Freq. Rate Max F003 1,000 R/W 2 [20.00 , 80.00] Hz
0x417A Freq. Rate Delay F003 1,000 R/W 2 [0.00 , 60.00] s
0x417C Snapshot Events F012 1,000 R/W 1 0=DISABLED
1=ENABLED
0x418F Confirmation address W 1
Ajustes Tierra Restringida Grupo 1 - Restricted Gnd Fault 1 Settings(Enhanced models only)
0x4224 Function F012 1 R/W 1 0=DISABLED
1=ENABLED
0x4225 Ground Fault Pickup F003 1 R/W 2 [0.02 , 20.00] CT
0x4227 Ground Fault Slope F003 1 R/W 2 [0.00 , 100.00] %
0x4229 Ground Fault Delay F003 1 R/W 2 [0.00 , 600.00] s
0x422B Snapshot Events F012 1 R/W 1 0=DISABLED
1=ENABLED
0x4235 Confirmation address W 1
Ajustes Tierra Restringida Grupo 2 - Restricted Gnd Fault 2 Settings(Enhanced models only)
0x4236 Function F012 1 R/W 1 0=DISABLED
1=ENABLED
0x4237 Ground Fault Pickup F003 1 R/W 2 [0.02 , 20.00] CT
0x4239 Ground Fault Slope F003 1 R/W 2 [0.00 , 100.00] %
0x423B Ground Fault Delay F003 1 R/W 2 [0.00 , 600.00] s
0x423D Snapshot Events F012 1 R/W 1 0=DISABLED
1=ENABLED
0x4247 Confirmation address W 1
Ajustes Tierra Restringida Grupo 3 - Restricted Gnd Fault 3 Settings(Enhanced models only)
0x4248 Function F012 1 R/W 1 0=DISABLED
1=ENABLED
0x4249 Ground Fault Pickup F003 1 R/W 2 [0.02 , 20.00] CT
0x424B Ground Fault Slope F003 1 R/W 2 [0.00 , 100.00] %
0x424D Ground Fault Delay F003 1 R/W 2 [0.00 , 600.00] s
0x424F Snapshot Events F012 1 R/W 1 0=DISABLED
1=ENABLED
0x4259 Confirmation address W 1
Ajustes Salto Vector Grupo 1 - Loss of Mains 1 Settings(Enhanced models only)
0x425A Function F012 1 R/W 1 0=DISABLED
1=ENABLED
0x425B Loss of Mains Mode F012 1 R/W 1 0=ONE PHASE
0x425C Phase Shift Angle F003 1 R/W 2 [2.00 , 22.00] Deg
0x425E Minimum Voltage F003 1 R/W 2 [30 , 500] V
0x4260 Snapshot Events F012 1 R/W 1 0=DISABLED
1=ENABLED
ADDRESS BIT NAME FORMAT STEP MODE LENGTH MISCELLANEOUS