GEK-113285A G650 Generator Protection & Control System B-127
APPENDIX B B.7 MEMORY MAP
B
Ajustes Derivada de Frecuencia 3-Frequency Rate of Change 3 Settings
0x4170 Function F012 1,000 R/W 1 0=DISABLED
1=ENABLED
0x4171 Freq. Rate Trend F012 1,000 R/W 1 0=INCREASING
1=DECREASING
2=BI-DIRECTIONAL
0x4172 Freq. Rate Pickup F003 1,000 R/W 2 [0.10 , 10.00] Hz/s
0x4174 Freq. Rate OV Supv F003 1,000 R/W 2 [0.00 , 110.00] %
0x4176 Freq. Rate Min F003 1,000 R/W 2 [20.00 , 80.00] Hz
0x4178 Freq. Rate Max F003 1,000 R/W 2 [20.00 , 80.00] Hz
0x417A Freq. Rate Delay F003 1,000 R/W 2 [0.00 , 60.00] s
0x417C Snapshot Events F012 1,000 R/W 1 0=DISABLED
1=ENABLED
0x418F Confirmation address W 1
Ajustes Tierra Restringida Grupo 1 - Restricted Gnd Fault 1 Settings(Enhanced models only)
0x4224 Function F012 1 R/W 1 0=DISABLED
1=ENABLED
0x4225 Ground Fault Pickup F003 1 R/W 2 [0.02 , 20.00] CT
0x4227 Ground Fault Slope F003 1 R/W 2 [0.00 , 100.00] %
0x4229 Ground Fault Delay F003 1 R/W 2 [0.00 , 600.00] s
0x422B Snapshot Events F012 1 R/W 1 0=DISABLED
1=ENABLED
0x4235 Confirmation address W 1
Ajustes Tierra Restringida Grupo 2 - Restricted Gnd Fault 2 Settings(Enhanced models only)
0x4236 Function F012 1 R/W 1 0=DISABLED
1=ENABLED
0x4237 Ground Fault Pickup F003 1 R/W 2 [0.02 , 20.00] CT
0x4239 Ground Fault Slope F003 1 R/W 2 [0.00 , 100.00] %
0x423B Ground Fault Delay F003 1 R/W 2 [0.00 , 600.00] s
0x423D Snapshot Events F012 1 R/W 1 0=DISABLED
1=ENABLED
0x4247 Confirmation address W 1
Ajustes Tierra Restringida Grupo 3 - Restricted Gnd Fault 3 Settings(Enhanced models only)
0x4248 Function F012 1 R/W 1 0=DISABLED
1=ENABLED
0x4249 Ground Fault Pickup F003 1 R/W 2 [0.02 , 20.00] CT
0x424B Ground Fault Slope F003 1 R/W 2 [0.00 , 100.00] %
0x424D Ground Fault Delay F003 1 R/W 2 [0.00 , 600.00] s
0x424F Snapshot Events F012 1 R/W 1 0=DISABLED
1=ENABLED
0x4259 Confirmation address W 1
Ajustes Salto Vector Grupo 1 - Loss of Mains 1 Settings(Enhanced models only)
0x425A Function F012 1 R/W 1 0=DISABLED
1=ENABLED
0x425B Loss of Mains Mode F012 1 R/W 1 0=ONE PHASE
0x425C Phase Shift Angle F003 1 R/W 2 [2.00 , 22.00] Deg
0x425E Minimum Voltage F003 1 R/W 2 [30 , 500] V
0x4260 Snapshot Events F012 1 R/W 1 0=DISABLED
1=ENABLED
ADDRESS BIT NAME FORMAT STEP MODE LENGTH MISCELLANEOUS