GEK-113285A G650 Generator Protection & Control System B-129
APPENDIX B B.7 MEMORY MAP
B
Ajustes Desequilibrio de Generador Grupo 2 - Generator Unbalance 2 Settings
0x42A9 Function F012 1 R/W 1 0=DISABLED
1=ENABLED
0x42AA Gen Unbal Inom F003 1 R/W 2 [0.00 , 10.00] A
0x42AC Gen Unbal Stg1 Pkp F003 1 R/W 2 [0.00 , 100.00] %
0x42AE Gen Unbal Stg1 K F003 1 R/W 2 [0.00 , 100.00]
0x42B0 Gen Unbal Stg1 Tmin F003 1 R/W 2 [0.0 , 1000.0] s
0x42B2 Gen Unbal Stg1 Tmax F003 1 R/W 2 [0.0 , 1000.0] s
0x42B4 Gen Unbal Stg1 K-Rst F003 1 R/W 2 [0.0 , 1000.0]
0x42B6 Gen Unbal Stg2 Pkp F003 1 R/W 2 [0.00 , 100.00] %
0x42B8 Gen Unbal Stg2 Delay F003 1 R/W 2 [0.0 , 1000.0] s
0x42BA Snapshot Events F012 1 R/W 1 0=DISABLED
1=ENABLED
0x42C4 Confirmation address W 1
Ajustes Desequilibrio de Generador Grupo 3 - Generator Unbalance 3 Settings
0x42C5 Function F012 1 R/W 1 0=DISABLED
1=ENABLED
0x42C6 Gen Unbal Inom F003 1 R/W 2 [0.00 , 10.00] A
0x42C8 Gen Unbal Stg1 Pkp F003 1 R/W 2 [0.00 , 100.00] %
0x42CA Gen Unbal Stg1 K F003 1 R/W 2 [0.00 , 100.00]
0x42CC Gen Unbal Stg1 Tmin F003 1 R/W 2 [0.0 , 1000.0] s
0x42CE Gen Unbal Stg1 Tmax F003 1 R/W 2 [0.0 , 1000.0] s
0x42D0 Gen Unbal Stg1 K-Rst F003 1 R/W 2 [0.0 , 1000.0]
0x42D2 Gen Unbal Stg2 Pkp F003 1 R/W 2 [0.00 , 100.00] %
0x42D4 Gen Unbal Stg2 Delay F003 1 R/W 2 [0.0 , 1000.0] s
0x42D6 Snapshot Events F012 1 R/W 1 0=DISABLED
1=ENABLED
0x42E0 Confirmation address W 1
Ajustes Voltios/ Hercios Grupo 1 - Volts per Hertz 1 Settings(Enhanced models only)
0x42E1 Function F012 1 R/W 1 0=DISABLED
1=ENABLED
0x42E2 V/Hz Source F012 1 R/W 1 0=PHASES
1=AUX VOLTAGE
0x42E3 V/Hz Minimum Voltage F003 1 R/W 2 [30.00 , 500.00] V
0x42E5 V/Hz Pickup Level F003 1 R/W 2 [0.80 , 4.00] pu
0x42E7 V/Hz Curve F012 1 R/W 1 0=DEFINITE TIME
1=CURVE A
2=CURVE B
3=CURVE C
0x42E8 V/Hz TD Multiplier F003 1 R/W 2 [0.05 , 600.00]
0x42EA V/Hz Reset Delay F003 1 R/W 2 [0.0 , 900.0] s
0x42EC Snapshot Events F012 1 R/W 1 0=DISABLED
1=ENABLED
0x42F6 Confirmation address W 1
Ajustes Voltios/ Hercios Grupo 2 - Volts per Hertz 2 Settings(Enhanced models only)
0x42F7 Function F012 1 R/W 1 0=DISABLED
1=ENABLED
0x42F8 V/Hz Source F012 1 R/W 1 0=PHASES
1=AUX VOLTAGE
0x42F9 V/Hz Minimum Voltage F003 1 R/W 2 [30.00 , 500.00] V
0x42FB V/Hz Pickup Level F003 1 R/W 2 [0.80 , 4.00] pu
0x42FD V/Hz Curve F012 1 R/W 1 0=DEFINITE TIME
1=CURVE A
ADDRESS BIT NAME FORMAT STEP MODE LENGTH MISCELLANEOUS