GEK-113285A G650 Generator Protection & Control System F-27
APPENDIX F F.2 FACTORY DEFAULT CONFIGURATION
F
DEMAND RESET INP Not Configured
FREEZE ENERGY CNT Not Configured
UNFREEZE ENERGY
CNT
Not Configured
RESET ENERGY CNT Not Configured
RESET KI2t COUNTERS Not Configured
RESET BKR COUNTERS Not Configured
Note (*): Only available for Enhanced models (see ordering code)
SETPOINT>RELAY CONFIGURATION>OSCILLOGRAPHY
DIGITAL CHANNEL NAME SOURCE SIGNAL LOGIC SOURCE LOGIC
DIG_CHANNEL#1 TRIP VO_083_GENERAL_TRIP
DIG_CHANNEL#2 50/51P TRIP VO_019_PHASE_OVERCURRENT_TRIP
DIG_CHANNEL#3 50/51G TRIP VO_069_GROUND_OVERCURRENT_T
RIP
DIG_CHANNEL#4 50_2/51_2 TRIP VO_061_51-2_TRIP
VO_041_50-1_TRIP
DIG_CHANNEL#5 27 TRIP VO_073_27P_TRIP
DIG_CHANNEL#6 59 TRIP VO_074_59P_TRIP
DIG_CHANNEL#7 81O81U TRIP VO_081_81U_TRIP
VO_080_81O_TRIP
DIG_CHANNEL#8 81DFDT TRIP VO_060_81DF-DT TRIP
DIG_CHANNEL#9 PICKUP VO_085_GENERAL_PKP
DIG_CHANNEL#10 50/51P PICKUP VO_007_PHASE_OVERCURRENT_PKP
DIG_CHANNEL#11 50/51G PICKUP VO_009_GROUND_OVERCURRENT_P
KP
DIG_CHANNEL#12 50_2/51_2 PKP VO_033_50-2_PKP
VO_006_51-2_PKP
DIG_CHANNEL#13 27 PICKUP VO_045_27P_PKP
DIG_CHANNEL#14 59 PICKUP VO_046_59P_PKP
DIG_CHANNEL#15 81U/O PICKUP VO_055_81U_PKP
VO_054_81O_PKP
DIG_CHANNEL#16 81R PICKUP VO_052_81DF-DT PKP
OSCILLO TRIGGER OSCILLO TRIGGER OPERATION BIT 8
VO_083_GENERAL_TRIP
SETPOINT>RELAY CONFIGURATION>OPERATIONS
OPERATION OPERATION TEXT SETTINGS VALUE/SOURCE
Operation1 CLOSE BREAKER
INTERLOCK(LOGIC) SYNCHK CLOSE PERM
FINAL STATES AND LOGIC BREAKER CLOSED
FRONT KEY I Key
INPUT Not configured
VIRTUAL OUTPUT Not configured
TIMEOUT 1000
CHANNELS ALL
SETPOINT>RELAY CONFIGURATION>PROTECTION ELEMENTS
PROTECTION ELEMENT SOURCE SIGNAL LOGIC SOURCE LOGIC