GEK-113000T F650 Digital Bay Controller C-15
APPENDIX C C.1 FACTORY DEFAULT SETTINGS
C
SETPOINT > CONTROL ELEMENTS > OVERFREQUENCY
OVERFREQUENCY 1 > OVERFREQUENCY 2 > OVERFREQUENCY 3
SETTING DESCRIPTION NAME DEFAULT VALUE STEP RANGE
USER
VALUE
Function permission Function DISABLED N/A [DISABLED – ENABLED]
Pickup level Pickup Level 50.50 0.01 Hz [20.00 : 65.00]
Trip time Trip Delay 0.00 0.01 s [0.00 : 900.00]
Reset time Reset Delay 0.00 0.01 s [0.00 : 900.00]
Minimum voltage threshold Minimum Voltage 30 1 V [30 : 300]
Snapshot event generation Snapshot Events ENABLED N/A [DISABLED – ENABLED]
SETPOINT > CONTROL ELEMENTS > SYNCHROCHECK
SETTING DESCRIPTION NAME DEFAULT VALUE STEP RANGE
USER
VALUE
Function permission Function DISABLED N/A [DISABLED – ENABLED]
Dead bus voltage level Dead Bus Level 10.00 0.01 V [0.00 : 300.00]
Live bus voltage level Live Bus Level 50.00 0.01 V [0.00 : 300.00]
Dead line voltage level Dead Line Level 10.00 0.01 V [0.00 : 300.00]
Live line voltage level Live Line Level 50.00 0.01 V [0.00 : 300.00]
Voltage Difference Max Volt Difference 10.00 0.01 V [2.00 : 300.00]
Angle Difference Max Angle Difference 10.0 0.1 Deg [2.0 : 80.0]
Frequency Slip Max Freq Difference 20 10 mHz [10 : 5000]
Breaker Closing time Time 0.50 0.01 s [0.01 : 600.00]
Dead Line – Dead Bus Function
permission
DL-DB Function DISABLED N/A [DISABLED – ENABLED]
Live Line – Dead Bus Function
permission
LL-DB Function DISABLED N/A [DISABLED – ENABLED]
Dead Line – Live Bus Function
permission
DL-LB Function DISABLED N/A [DISABLED – ENABLED]
Snapshot event generation Snapshot Events ENABLED N/A [DISABLED – ENABLED]
SETPOINT > CONTROL ELEMENTS > AUTORECLOSE
SETTING DESCRIPTION NAME DEFAULT VALUE STEP RANGE
USER
VALUE
Function permission Function DISABLED N/A [DISABLED – ENABLED]
Maximum Number of shots Max Number Shots 1 N/A [1 : 4]
Dead time 1 Dead Time 1 0.00 0.01 s [0.00 : 900.00]
Dead time 2 Dead Time 2 0.00 0.01 s [0.00 : 900.00]
Dead time 3 Dead Time 3 0.00 0.01 s [0.00 : 900.00]
Dead time 4 Dead Time 4 0.00 0.01 s [0.00 : 900.00]
Reclaim time or reset lockout delay Reclaim Time 0.00 0.01 s [0.00 : 900.00]
Reclose conditions permission Cond. Permission DISABLED N/A [DISABLED – ENABLED]
Hold time Hold Time 0.00 0.01 s [0.00 : 900.00]
Reset time Reset Time 0.00 0.01 s [0.00 : 900.00]
Snapshot event generation Snapshot Events ENABLED N/A [DISABLED – ENABLED]