C-16 F650 Digital Bay Controller GEK-113000T
C.1 FACTORY DEFAULT SETTINGS APPENDIX C
C
SETPOINT > CONTROL ELEMENTS > BREAKER FAILURE
SETTING DESCRIPTION NAME DEFAULT VALUE STEP RANGE
USER
VALUE
Function permission Function DISABLED N/A [DISABLED – ENABLED]
Supervision (retrip) pickup level Supervision Pickup 1.00 0.01 A [0.05 : 160.00]
Hiset pickup level Hiset Pickup 5.00 0.01 A [0.05 : 160.00]
Lowset pickup level Lowset Pickup 2.00 0.01 A [0.05 : 160.00]
Internal arc pickup level Internal Arc Pickup 0.10 0.01 A [0.05 : 160.00]
Internal arc time delay Internal Arc Delay 10.00 0.01 s [0.00 : 900.00]
Retrip time delay Supervision Delay 10.00 0.01 s [0.00 : 900.00]
Hiset time delay HiSet Delay 10.00 0.01 s [0.00 : 900.00]
Lowset time delay LowSet Delay 10.00 0.01 s [0.00 : 900.00]
Second stage time delay 2nd Step Delay 10.00 0.01 s [0.00 : 900.00]
WITHOUT current element time delay No Current Delay 10.00 0.01 s [0.00 : 900.00]
Snapshot event generation Snapshot Events ENABLED N/A [DISABLED – ENABLED]
SETPOINT > CONTROL ELEMENTS > VT FUSE FAILURE)
SETTING DESCRIPTION NAME DEFAULT VALUE STEP RANGE
USER
VALUE
Function permission Function
DISABLED
N/A [DISABLED – ENABLED]
Snapshot event generation Snapshot Events ENABLED N/A [DISABLED – ENABLED]
SETPOINT > CONTROL ELEMENTS > BROKEN CONDUCTOR
BROKEN CONDUCTOR 1 >BROKEN CONDUCTOR 2 >BROKEN CONDUCTOR 3
SETTING DESCRIPTION NAME DEFAULT VALUE STEP RANGE
USER
VALUE
Function permission Function DISABLED N/A [DISABLED – ENABLED]
Tap Level in percentage of I2/I1 Tap 20 0.10% [20.0 : 100.0]
Trip Time Trip Delay 60 0.01 s [0.00 : 900.00]
Snapshot event generation Snapshot Events ENABLED N/A [DISABLED – ENABLED]
Current Inhibition Level setting Operation Threshold 0.005 0.001 A [0.000 : 1.000]
SETPOINT > CONTROL ELEMENTS > LOCKED ROTOR
LOCKED ROTOR 1 >LOCKED ROTOR 2 >LOCKED ROTOR 3
SETTING DESCRIPTION NAME DEFAULT VALUE STEP RANGE
USER
VALUE
Function permission Function DISABLED N/A [DISABLED – ENABLED]
Input type Input PHASOR(DFT) N/A [PHASOR – RMS]
Full load current Full Load Current 0.50 KA [0.10 : 10.00]
Pickup level Pickup Level 1.01 N/A [1.01 : 109.00]
Trip time Trip Delay 0.00 s [0.00 : 900.00]
Reset time Reset Delay 0.00 s [0.00 : 900.00]
Snapshot event generation Snapshot Events ENABLED N/A [DISABLED – ENABLED]