Programming the outputs
LOCATION 45 - AUXILIARY OUTPUT 1-4 PARTITION SELECTION (4 segments, feature selection data)
Location 45 is used to select the partition(s) in which the events must occur before the output
(relay) will activate. Location 45 has 4 segments. Segment 1 corresponds to output 1, and
segment 2 corresponds to output 2, segments 3 and 4 correspond to outputs 3 and 4.
Segment 1
(Auxiliary 1)
Segment 2
(Auxiliary 2)
Segment 3
(Auxiliary)
Segment 4
(Auxiliary)
1= Partition #1 1= Partition #1 1= Partition #1 1= Partition #1
2= Partition #2 2= Partition #2 2= Partition #2 2= Partition #2
3= Partition #3 3= Partition #3 3= Partition #3 3= Partition #3
4= Partition #4 4= Partition #4 4= Partition #4 4= Partition #4
5= Partition #5 5= Partition #5 5= Partition #5 5= Partition #5
6= Partition #6 6= Partition #6 6= Partition #6 6= Partition #6
7= Partition #7 7= Partition #7 7= Partition #7 7= Partition #7
8= Partition #8 8= Partition #8 8= Partition #8 8= Partition #8
LOCATION 46 - AUXILIARY OUTPUT 1-4 SPECIAL TIMING (4 segments, feature selection data)
Location 46 contains special timing feature activation for the 4 auxiliary outputs (relays).
Segment 1 corresponds to output 1, segment 2 corresponds to output 2. Segments 3 and 4
correspond to outputs 3-4.
Segment 1-4
1 = On: if output should be timed in minutes; Off: if timed in seconds
2 = On: if output should latch; Off: if output should be timed
3 = On: if output should stop timing when the code is entered; Off: if
the output should continue to time when the code is entered
4 = On: if output should only activate between the closing and
opening time in locations 52 and 53
5 = On: if output should only activate between the opening and
closing time in locations 52 and 53
6 = On: if output should be inverted (0 volts going to 12 volts when
activated)
7 = Reserved
8 = Reserved
LOCATION 47 - AUXILIARY OUTPUT 1 (relay 1 and open collector 1), EVENT AND TIME (2 segments, numerical
data)
Segment 1
Use the chart below to select the event that will activate auxiliary output 1
(relay 1)
Segment 2
Program the timing from 0-255 (minutes or seconds, depending on the
data programmed in segment 1, location 46). Programming a “0” makes
the output follow the event
NX-8-EUR Installation manual Page 57 02/07/06