The following commands are still allowed:
R
ead settings, statuses, measurands
Read records (event, fault, disturbance)
Time Synchronisation
Change active setting group
8.3 IEC 61850 PROTOCOL BLOCKING
If Read-Only Mode is enabled for the Ethernet interfacing with IEC 61850, the following commands are blocked at
the inter
face:
All controls, including:
Enable/disable protection
Operate Control Inputs
CB operations (Close/Trip, Lock)
Reset LEDs
The following commands are still allowed:
Read statuses, measurands
Generate reports
Extract disturbance records
Time synchronisation
Change active setting group
8.4 READ-ONLY SETTINGS
The following settings are available for enabling or disabling Read Only Mode.
RP1 R
ead Only
RP2 Read Only (only for products that have RP2)
NIC Read Only (where Ethernet is available)
8.5 READ-ONLY DDB SIGNALS
The remote read only mode is also available in the PSL using three dedicated DDB signals:
RP1 R
ead Only
RP2 Read Only (only for products that have RP2)
NIC Read Only (where Ethernet is available)
Using the PSL, these signals can be activated by opto-inputs, Control Inputs and function keys if required.
P54A/B/C/E Chapter 17 - Communications