Installation Guide SG Series 10-20-30-40 UL S
NEC SECTION 210-20 (a)
Table 310-16. Allowable Ampacities of Insulated Conductors Rated O Through 2000 Volts, 60°C Trough
90°C (140°F Trough 194°F) Not More than Three Current-Carrying Conductors in Raceway, Cable, or
Earth (Directly Buried), Based on Ambient Temperature of 30°C (86°F).
Temperature Rating of Conductor (See table 310-13)
Types
FEPW, RH, RHW,
THHW, THW,
THWN, XHHW,
USE, ZW
Types
TBS, SA, SIS, FEP,
FEPB, MI, RHH,
RHW-2, THHN,
THHW, THW-2,
THWN-2, USE-2,
XHH, XHHW,
XHHW-2,ZW-2
Types
RH, RHW,
THHW,
THW, THWN,
XHHW, USE
Types
TBS, SA, SIS,
THHN, THHW,
THW-2,
THWN-2, RHH,
RHW-2, USE-2,
XHH, XHHW,
XHHW-2,
ZW-2
ALUMINIUM or COPPER-CLAD ALUMINIUM
For ambient temperatures other than 30°C (86°F), multiply the allowable ampacities shown above by the appropriate factor
below