EasyManua.ls Logo

GE SG Series

GE SG Series
46 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Critical Power
Modifications reserved
Page 36/46
GE_UPS_OPM_SGS_ISG_10K_40K_0US_V070.docx
Installation Guide SG Series 10-20-30-40 UL S
3.9 RPA PARALLEL SYSTEM CONNECTION
WARNING !
This operation must be performed by QUALIFIED SERVICE PERSONNEL ONLY before
the initial start-up.
ENSURE THAT THE UPS INSTALLATION IS COMPLETELY POWERED DOWN.
3.9.1 Power wiring of parallel units
To guarantee good Load sharing between the units of a parallel system, we recommend that the cable
length from the input distribution board (5) to the output distribution board (10) is equal for each unit
(a+b = c+d = e+f = g+h = i+l = m+n = o+p = q+r).
Tolerance: +/-10%.
The AC input power of the Bypass must be the same for all units of the parallel system - no phase shift
allowed between units.
NOTE !
It is strongly recommended that no transformers, automatic circuit breakers or fuses
should be inserted between the unit’s output and the Load common bus bars.
However, it is recommended that a disconnection or isolation switch is installed in
order to totally isolate a unit if needed.
Fig. 3.9.1-1 Power wiring of RPA Parallel System
1
=
Rectifier
2
=
Inverter
3
=
Automatic Bypass
4
=
Manual Bypass
5
=
Input Utility Distribution
6
=
Unit Output Load
7
=
External Battery fuse or
MCB
8
=
External Battery
9
=
Common bus-bar and
Output Load Distribution
=
UPS Number 1
=
UPS Number 2
=
UPS Number 3
=
UPS Number 4
=
UPS Number 5
=
UPS Number 6
=
UPS Number 7
=
UPS Number 8

Related product manuals