GE Multilin L60 Line Phase Comparison System B-41
APPENDIX B B.4 MEMORY MAPPING
B
8C80 ...Repeated for Digital Element 33
8C94 ...Repeated for Digital Element 34
8CA8 ...Repeated for Digital Element 35
8CBC ...Repeated for Digital Element 36
8CD0 ...Repeated for Digital Element 37
8CE4 ...Repeated for Digital Element 38
8CF8 ...Repeated for Digital Element 39
8D0C ...Repeated for Digital Element 40
8D20 ...Repeated for Digital Element 41
8D34 ...Repeated for Digital Element 42
8D48 ...Repeated for Digital Element 43
8D5C ...Repeated for Digital Element 44
8D70 ...Repeated for Digital Element 45
8D84 ...Repeated for Digital Element 46
8D98 ...Repeated for Digital Element 47
8DAC ...Repeated for Digital Element 48
Trip Bus (Read/Write Setting)
8E00 Trip Bus 1 Function 0 to 1 --- 1 F102 0 (Disabled)
8E01 Trip Bus 1 Block --- --- --- F300 0
8E02 Trip Bus 1 Pickup Delay 0 to 600 s 0.01 F001 0
8E03 Trip Bus 1 Reset Delay 0 to 600 s 0.01 F001 0
8E04 Trip Bus 1 Input 1 0 to 65535 --- 1 F300 0
8E05 Trip Bus 1 Input 2 0 to 65535 --- 1 F300 0
8E06 Trip Bus 1 Input 3 0 to 65535 --- 1 F300 0
8E07 Trip Bus 1 Input 4 0 to 65535 --- 1 F300 0
8E08 Trip Bus 1 Input 5 0 to 65535 --- 1 F300 0
8E09 Trip Bus 1 Input 6 0 to 65535 --- 1 F300 0
8E0A Trip Bus 1 Input 7 0 to 65535 --- 1 F300 0
8E0B Trip Bus 1 Input 8 0 to 65535 --- 1 F300 0
8E0C Trip Bus 1 Input 9 0 to 65535 --- 1 F300 0
8E0D Trip Bus 1 Input 10 0 to 65535 --- 1 F300 0
8E0E Trip Bus 1 Input 11 0 to 65535 --- 1 F300 0
8E0F Trip Bus 1 Input 12 0 to 65535 --- 1 F300 0
8E10 Trip Bus 1 Input 13 0 to 65535 --- 1 F300 0
8E11 Trip Bus 1 Input 14 0 to 65535 --- 1 F300 0
8E12 Trip Bus 1 Input 15 0 to 65535 --- 1 F300 0
8E13 Trip Bus 1 Input 16 0 to 65535 --- 1 F300 0
8E14 Trip Bus 1 Latching 0 to 1 --- 1 F102 0 (Disabled)
8E15 Trip Bus 1 Reset 0 to 65535 --- 1 F300 0
8E16 Trip Bus 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
8E16 Trip Bus 1 Events 0 to 1 --- 1 F102 0 (Disabled)
8E18 Reserved (8 items) --- --- --- F001 0
8E20 ...Repeated for Trip Bus 2
8E40 ...Repeated for Trip Bus 3
8E60 ...Repeated for Trip Bus 4
8E80 ...Repeated for Trip Bus 5
8EA0 ...Repeated for Trip Bus 6
FlexElement (Read/Write Setting) (16 modules)
9000 FlexElement™ 1 Function 0 to 1 --- 1 F102 0 (Disabled)
9001 FlexElement™ 1 Name --- --- --- F206 “FxE 1”
9004 FlexElement™ 1 InputP 0 to 65535 --- 1 F600 0
9005 FlexElement™ 1 InputM 0 to 65535 --- 1 F600 0
9006 FlexElement™ 1 Compare 0 to 1 --- 1 F516 0 (LEVEL)
9007 FlexElement™ 1 Input 0 to 1 --- 1 F515 0 (SIGNED)
Table B–9: MODBUS MEMORY MAP (Sheet 33 of 55)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT