GE Multilin T60 Transformer Protection System B-17
APPENDIX B B.4 MEMORY MAPPING
B
Phasor Measurement Unit Actual Values (Read Only)
2540 PMU 1 Phase A Voltage Magnitude 0 to 999999.999 V 0.001 F060 0
2542 PMU Unit 1 Phase A Voltage Angle -180 to 180 ° 0.01 F002 0
2543 PMU 1 Phase B Voltage Magnitude 0 to 999999.999 V 0.001 F060 0
2545 PMU 1 Phase B Voltage Angle -180 to 180 ° 0.01 F002 0
2546 PMU 1 Phase C Voltage Magnitude 0 to 999999.999 V 0.001 F060 0
2548 PMU 1 Phase C Voltage Angle -180 to 180 ° 0.01 F002 0
2549 PMU 1 Auxiliary Voltage Magnitude 0 to 999999.999 V 0.001 F060 0
254B PMU 1 Auxiliary Voltage Angle -180 to 180 ° 0.01 F002 0
254C PMU 1 Positive Sequence Voltage Magnitude 0 to 999999.999 V 0.001 F060 0
254E PMU 1 Positive Sequence Voltage Angle -180 to 180 ° 0.01 F002 0
254F PMU 1 Negative Sequence Voltage Magnitude 0 to 999999.999 V 0.001 F060 0
2551 PMU 1 Negative Sequence Voltage Angle -180 to 180 ° 0.01 F002 0
2552 PMU 1 Zero Sequence Voltage Magnitude 0 to 999999.999 V 0.001 F060 0
2554 PMU 1 Zero Sequence Voltage Angle -180 to 180 ° 0.01 F002 0
2555 PMU 1 Phase A Current Magnitude 0 to 999999.999 A 0.001 F060 0
2557 PMU 1 Phase A Current Angle -180 to 180 ° 0.01 F002 0
2558 PMU 1 Phase B Current Magnitude 0 to 999999.999 A 0.001 F060 0
255A PMU 1 Phase B Current Angle -180 to 180 ° 0.10 F002 0
255B PMU 1 Phase C Current Magnitude 0 to 999999.999 A 0.001 F060 0
255D PMU 1 Phase C Current Angle -180 to 180 ° 0.01 F002 0
255E PMU 1 Ground Current Magnitude 0 to 999999.999 A 0.001 F060 0
2560 PMU 1 Ground Current Angle -180 to 180 ° 0.01 F002 0
2561 PMU 1 Positive Sequence Current Magnitude 0 to 999999.999 A 0.001 F060 0
2563 PMU 1 Positive Sequence Current Angle -180 to 180 ° 0.01 F002 0
2564 PMU 1 Negative Sequence Current Magnitude 0 to 999999.999 A 0.001 F060 0
2566 PMU 1 Negative Sequence Current Angle -180 to 180 ° 0.01 F002 0
2567 PMU 1 Zero Sequence Current Magnitude 0 to 999999.999 A 0.001 F060 0
2569 PMU 1 Zero Sequence Current Angle -180 to 180 ° 0.01 F002 0
256A PMU 1 Frequency 2 to 90 Hz 0.001 F003 0
256C PMU 1 df/dt -327.67 to 327.67 Hz/s 0.01 F002 0
256D PMU 1 Configuration Change Counter 0 to 65535 --- 1 F001 0
256E Reserved (4 items) 0 to 1 --- 1 F001 0
Phasor Measurement Unit Integer (Read Only)
2608 PMU 1 SOC Timestamp 0 to 4294967295 seconds 1 F003 0
260A PMU 1 FRAMESEC Timestamp 0 to 4294967295 seconds 1 F003 0
260C PMU 1 STAT Flags 0 to 4294967295 --- 1 F003 0
Remote Double-Point Status Inputs (Read/Write Setting Registers) (5 modules)
2620 Remote Double-Point Status Input 1 Device 1 to 32 --- 1 F001 1
2621 Remote Double-Point Status Input 1 Item 0 to 64 --- 1 F606 0 (None)
2622 Remote Double-Point Status Input 1 Name 1 to 64 --- 1 F205 "RemDPS Ip 1"
2628 Remote Double-Point Status Input 1 Events 0 to 1 --- 1 F102 0 (Disabled)
2629 ... Repeated for Double-Point Status Input 2
2632 ... Repeated for Double-Point Status Input 3
263B ... Repeated for Double-Point Status Input 4
2644 ... Repeated for Double-Point Status Input 5
IEC 61850 GGIO5 Configuration (Read/Write Setting Registers) (16 modules)
26B0 IEC 61850 GGIO5 uinteger Input 1 Operand --- --- --- F612 0
26B1 IEC 61850 GGIO5 uinteger Input 2 Operand --- --- --- F612 0
26B2 IEC 61850 GGIO5 uinteger Input 3 Operand --- --- --- F612 0
26B3 IEC 61850 GGIO5 uinteger Input 4 Operand --- --- --- F612 0
26B4 IEC 61850 GGIO5 uinteger Input 5 Operand --- --- --- F612 0
26B5 IEC 61850 GGIO5 uinteger Input 6 Operand --- --- --- F612 0
26B6 IEC 61850 GGIO5 uinteger Input 7 Operand --- --- --- F612 0
Table B–10: MODBUS MEMORY MAP (Sheet 9 of 65)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT