B-16 T60 Transformer Protection System GE Multilin
B.4 MEMORY MAPPING APPENDIX B
B
21E8 Breaker 1 Operating Time Phase C 0 to 65535 ms 1 F001 0
21E9 Breaker 1 Operating Time 0 to 65535 ms 1 F001 0
21EA ...Repeated for Breaker Arcing Current 2
21F4 ...Repeated for Breaker Arcing Current 3
21FE ...Repeated for Breaker Arcing Current 4
Breaker Arcing Current Commands (Read/Write Command) (4 modules)
2224 Breaker 1 Arcing Current Clear Command 0 to 1 --- 1 F126 0 (No)
2225 Breaker 2 Arcing Current Clear Command 0 to 1 --- 1 F126 0 (No)
2226 Breaker 3 Arcing Current Clear Command 0 to 1 --- 1 F126 0 (No)
2227 Breaker 4 Arcing Current Clear Command 0 to 1 --- 1 F126 0 (No)
Passwords Unauthorized Access (Read/Write Command)
2230 Reset Unauthorized Access 0 to 1 --- 1 F126 0 (No)
Transformer Differential and Restraint (Read Only)
2300 Transformer Reference Winding 1 to 6 --- 1 F001 1
2301 Transformer Differential Phasor Iad Magnitude 0 to 30 pu 0.001 F001 0
2302 Transformer Differential Phasor Iad Angle -359.9 to 0 degrees 0.1 F002 0
2303 Transformer Restraint Phasor Iar Magnitude 0 to 30 pu 0.001 F001 0
2304 Transformer Restraint Phasor Iar Angle -359.9 to 0 degrees 0.1 F002 0
2305 Transformer Differential 2nd Harm Iad Magnitude 0 to 999.9 % fo 0.1 F001 0
2306 Transformer Differential 2nd Harm Iad Angle -359.9 to 0 degrees 0.1 F002 0
2307 Transformer Differential 5th Harm Iad Magnitude 0 to 999.9 % fo 0.1 F001 0
2308 Transformer Differential 5th Harm Iad Angle -359.9 to 0 degrees 0.1 F002 0
2309 Transformer Differential Phasor Ibd Magnitude 0 to 30 pu 0.001 F001 0
230A Transformer Differential Phasor Ibd Angle -359.9 to 0 degrees 0.1 F002 0
230B Transformer Restraint Phasor Ibr Magnitude 0 to 30 pu 0.001 F001 0
230C Transformer Restraint Phasor Ibr Angle -359.9 to 0 degrees 0.1 F002 0
230D Transformer Differential 2nd Harm Ibd Magnitude 0 to 999.9 % fo 0.1 F001 0
230E Transformer Differential 2nd Harm Ibd Angle -359.9 to 0 degrees 0.1 F002 0
230F Transformer Differential 5th Harm Ibd Magnitude 0 to 999.9 % fo 0.1 F001 0
2310 Transformer Differential 5th Harm Ibd Angle -359.9 to 0 degrees 0.1 F002 0
2311 Transformer Differential Phasor Icd Magnitude 0 to 30 pu 0.001 F001 0
2312 Transformer Differential Phasor Icd Angle -359.9 to 0 degrees 0.1 F002 0
2313 Transformer Restraint Phasor Icr Magnitude 0 to 30 pu 0.001 F001 0
2314 Transformer Restraint Phasor Icr Angle -359.9 to 0 degrees 0.1 F002 0
2315 Transformer Differential 2nd Harm Icd Magnitude 0 to 999.9 % fo 0.1 F001 0
2316 Transformer Differential 2nd Harm Icd Angle -359.9 to 0 degrees 0.1 F002 0
2317 Transformer Differential 5th Harm Icd Magnitude 0 to 999.9 % fo 0.1 F001 0
2318 Transformer Differential 5th Harm Icd Angle -359.9 to 0 degrees 0.1 F002 0
Transformer Thermal Inputs Actual Values (Read Only)
2330 Transformer Top Oil Temperature 0 to 300 °C 1 F002 0
2331 Transformer Hottest Spot Temperature 0 to 300 °C 1 F002 0
2332 Transformer Aging Factor 0 to 6553.5 PU 0.1 F001 0
2333 Transformer Daily Loss of Life 0 to 500000 Hours 1 F060 0
Transformer Thermal Inputs Actual Values (Read Only Non-Volatile)
2335 Transformer Loss of Life 0 to 500000 Hours 1 F060 0
Synchrocheck Actual Values (Read Only) (2 modules)
2400 Synchrocheck 1 Delta Voltage -1000000000000 to
1000000000000
V 1 F060 0
2402 Synchrocheck 1 Delta Frequency 0 to 655.35 Hz 0.01 F001 0
2403 Synchrocheck 1 Delta Phase 0 to 359.9 degrees 0.1 F001 0
2404 ...Repeated for Synchrocheck 2
Filed Unit Raw Data Settings (Read/Write Setting)
2460 Field Raw Data Port 0 to 7 --- 1 F244 6 (H1a)
2461 Filed Raw Data Freeze 0 to 1 --- 1 F102 0 (Disabled)
Table B–10: MODBUS MEMORY MAP (Sheet 8 of 65)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT