B-30 T60 Transformer Protection System GE Multilin
B.4 MEMORY MAPPING APPENDIX B
B
4679 ...Repeated for Transformer Winding 4
468C ...Repeated for Transformer Winding 5
469F ...Repeated for Transformer Winding 6
Breaker Control (Read/Write Settings) (6 modules)
4700 Breaker 1 Function 0 to 1 --- 1 F102 0 (Disabled)
4701 Breaker 1 Name --- --- --- F206 “Bkr 1"
4704 Breaker 1 Mode 0 to 1 --- 1 F157 0 (3-Pole)
4705 Breaker 1 Open 0 to 65535 --- 1 F300 0
4706 Breaker 1 Close 0 to 65535 --- 1 F300 0
4707 Breaker 1 Phase A / Three-pole Closed 0 to 65535 --- 1 F300 0
4708 Breaker 1 Phase B Closed 0 to 65535 --- 1 F300 0
4709 Breaker 1 Phase C Closed 0 to 65535 --- 1 F300 0
470A Breaker 1 External Alarm 0 to 65535 --- 1 F300 0
470B Breaker 1 Alarm Delay 0 to 65.535 s 0.001 F003 0
470D Breaker 1 Pushbutton Control 0 to 1 --- 1 F102 0 (Disabled)
470E Breaker 1 Manual Close Recall Time 0 to 65.535 s 0.001 F003 0
4710 Breaker 1 Out of Service 0 to 65535 --- 1 F300 0
4711 Breaker 1 Block Open 0 to 65535 --- 1 F300 0
4712 Breaker 1 Block Close 0 to 65535 --- 1 F300 0
4713 Breaker 1 Phase A / Three-pole Opened 0 to 65535 --- 1 F300 0
4714 Breaker 1 Phase B Opened 0 to 65535 --- 1 F300 0
4715 Breaker 1 Phase C Opened 0 to 65535 --- 1 F300 0
4716 Breaker 1 Operate Time 0 to 65.535 s 0.001 F001 70
4717 Breaker 1 Events 0 to 1 --- 1 F102 0 (Disabled)
4718 Reserved 0 to 65535 s 1 F001 0
4719 ...Repeated for Breaker 2
4732 ...Repeated for Breaker 3
474B ...Repeated for Breaker 4
4764 ...Repeated for Breaker 5
477D ...Repeated for Breaker 6
Synchrocheck (Read/Write Setting) (2 modules)
47A0 Synchrocheck 1 Function 0 to 1 --- 1 F102 0 (Disabled)
47A1 Synchrocheck 1 V1 Source 0 to 5 --- 1 F167 0 (SRC 1)
47A2 Synchrocheck 1 V2 Source 0 to 5 --- 1 F167 1 (SRC 2)
47A3 Synchrocheck 1 Maximum Voltage Difference 0 to 400000 V 1 F060 10000
47A5 Synchrocheck 1 Maximum Angle Difference 0 to 100 degrees 1 F001 30
47A6 Synchrocheck 1 Maximum Frequency Difference 0 to 2 Hz 0.01 F001 100
47A7 Synchrocheck 1 Dead Source Select 0 to 5 --- 1 F176 1 (LV1 and DV2)
47A8 Synchrocheck 1 Dead V1 Maximum Voltage 0 to 1.25 pu 0.01 F001 30
47A9 Synchrocheck 1 Dead V2 Maximum Voltage 0 to 1.25 pu 0.01 F001 30
47AA Synchrocheck 1 Live V1 Minimum Voltage 0 to 1.25 pu 0.01 F001 70
47AB Synchrocheck 1 Live V2 Minimum Voltage 0 to 1.25 pu 0.01 F001 70
47AC Synchrocheck 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
47AD Synchrocheck 1 Events 0 to 1 --- 1 F102 0 (Disabled)
47AE Synchrocheck 1 Block 0 to 65535 --- 1 F300 0
47AF Synchrocheck 1 Frequency Hysteresis 0 to 0.1 Hz 0.01 F001 6
47B0 ...Repeated for Synchrocheck 2
Demand (Read/Write Setting)
47D0 Demand Current Method 0 to 2 --- 1 F139 0 (Thermal Exponentia
l)
47D1 Demand Power Method 0 to 2 --- 1 F139 0 (Thermal Exponentia
l)
47D2 Demand Interval 0 to 5 --- 1 F132 2 (15 MIN)
47D3 Demand Input 0 to 65535 --- 1 F300 0
Table B–10: MODBUS MEMORY MAP (Sheet 22 of 65)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT