B-34 T60 Transformer Protection System GE Multilin
B.4 MEMORY MAPPING APPENDIX B
B
5903 Phase Time Overcurrent 1 Pickup 0 to 30 pu 0.001 F001 1000
5904 Phase Time Overcurrent 1 Curve 0 to 16 --- 1 F103 0 (IEEE Mod Inv)
5905 Phase Time Overcurrent 1 Multiplier 0 to 600 --- 0.01 F001 100
5906 Phase Time Overcurrent 1 Reset 0 to 1 --- 1 F104 0 (Instantaneous)
5907 Phase Time Overcurrent 1 Voltage Restraint 0 to 1 --- 1 F102 0 (Disabled)
5908 Phase TOC 1 Block For Each Phase (3 items) 0 to 65535 --- 1 F300 0
590B Phase Time Overcurrent 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
590C Phase Time Overcurrent 1 Events 0 to 1 --- 1 F102 0 (Disabled)
590D Reserved (3 items) 0 to 1 --- 1 F001 0
5910 ...Repeated for Phase Time Overcurrent 2
5920 ...Repeated for Phase Time Overcurrent 3
5930 ...Repeated for Phase Time Overcurrent 4
5940 ...Repeated for Phase Time Overcurrent 5
5950 ...Repeated for Phase Time Overcurrent 6
Phase Instantaneous Overcurrent (Read/Write Grouped Setting) (12 modules)
5A00 Phase Instantaneous Overcurrent 1 Function 0 to 1 --- 1 F102 0 (Disabled)
5A01 Phase Instantaneous Overcurrent 1 Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
5A02 Phase Instantaneous Overcurrent 1 Pickup 0 to 30 pu 0.001 F001 1000
5A03 Phase Instantaneous Overcurrent 1 Delay 0 to 600 s 0.01 F001 0
5A04 Phase Instantaneous Overcurrent 1 Reset Delay 0 to 600 s 0.01 F001 0
5A05 Phase IOC1 Block For Phase A 0 to 65535 --- 1 F300 0
5A06 Phase IOC1 Block For Phase B 0 to 65535 --- 1 F300 0
5A07 Phase IOC1 Block For Phase C 0 to 65535 --- 1 F300 0
5A08 Phase Instantaneous Overcurrent 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
5A09 Phase Instantaneous Overcurrent 1 Events 0 to 1 --- 1 F102 0 (Disabled)
5A0A Reserved (6 items) 0 to 1 --- 1 F001 0
5A10 ...Repeated for Phase Instantaneous Overcurrent 2
5A20 ...Repeated for Phase Instantaneous Overcurrent 3
5A30 ...Repeated for Phase Instantaneous Overcurrent 4
5A40 ...Repeated for Phase Instantaneous Overcurrent 5
5A50 ...Repeated for Phase Instantaneous Overcurrent 6
5A60 ...Repeated for Phase Instantaneous Overcurrent 7
5A70 ...Repeated for Phase Instantaneous Overcurrent 8
5A80 ...Repeated for Phase Instantaneous Overcurrent 9
5A90 ...Repeated for Phase Instantaneous Overcurrent 10
5AA0 ...Repeated for Phase Instantaneous Overcurrent 11
5AB0 ...Repeated for Phase Instantaneous Overcurrent 12
Neutral Time Overcurrent (Read/Write Grouped Setting) (6 modules)
5B00 Neutral Time Overcurrent 1 Function 0 to 1 --- 1 F102 0 (Disabled)
5B01 Neutral Time Overcurrent 1 Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
5B02 Neutral Time Overcurrent 1 Input 0 to 1 --- 1 F122 0 (Phasor)
5B03 Neutral Time Overcurrent 1 Pickup 0 to 30 pu 0.001 F001 1000
5B04 Neutral Time Overcurrent 1 Curve 0 to 16 --- 1 F103 0 (IEEE Mod Inv)
5B05 Neutral Time Overcurrent 1 Multiplier 0 to 600 --- 0.01 F001 100
5B06 Neutral Time Overcurrent 1 Reset 0 to 1 --- 1 F104 0 (Instantaneous)
5B07 Neutral Time Overcurrent 1 Block 0 to 65535 --- 1 F300 0
5B08 Neutral Time Overcurrent 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
5B09 Neutral Time Overcurrent 1 Events 0 to 1 --- 1 F102 0 (Disabled)
5B0A Reserved (6 items) 0 to 1 --- 1 F001 0
5B10 ...Repeated for Neutral Time Overcurrent 2
5B20 ...Repeated for Neutral Time Overcurrent 3
5B30 ...Repeated for Neutral Time Overcurrent 4
5B40 ...Repeated for Neutral Time Overcurrent 5
5B50 ...Repeated for Neutral Time Overcurrent 6
Table B–10: MODBUS MEMORY MAP (Sheet 26 of 65)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT