GE Multilin T60 Transformer Protection System B-35
APPENDIX B B.4 MEMORY MAPPING
B
Neutral Instantaneous Overcurrent (Read/Write Grouped Setting) (12 modules)
5C00 Neutral Instantaneous Overcurrent 1 Function 0 to 1 --- 1 F102 0 (Disabled)
5C01 Neutral Instantaneous Overcurrent 1 Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
5C02 Neutral Instantaneous Overcurrent 1 Pickup 0 to 30 pu 0.001 F001 1000
5C03 Neutral Instantaneous Overcurrent 1 Delay 0 to 600 s 0.01 F001 0
5C04 Neutral Instantaneous Overcurrent 1 Reset Delay 0 to 600 s 0.01 F001 0
5C05 Neutral Instantaneous Overcurrent 1 Block 0 to 65535 --- 1 F300 0
5C06 Neutral Instantaneous Overcurrent 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
5C07 Neutral Instantaneous Overcurrent 1 Events 0 to 1 --- 1 F102 0 (Disabled)
5C08 Reserved (8 items) 0 to 1 --- 1 F001 0
5C10 ...Repeated for Neutral Instantaneous Overcurrent 2
5C20 ...Repeated for Neutral Instantaneous Overcurrent 3
5C30 ...Repeated for Neutral Instantaneous Overcurrent 4
5C40 ...Repeated for Neutral Instantaneous Overcurrent 5
5C50 ...Repeated for Neutral Instantaneous Overcurrent 6
5C60 ...Repeated for Neutral Instantaneous Overcurrent 7
5C70 ...Repeated for Neutral Instantaneous Overcurrent 8
5C80 ...Repeated for Neutral Instantaneous Overcurrent 9
5C90 ...Repeated for Neutral Instantaneous Overcurrent 10
5CA0 ...Repeated for Neutral Instantaneous Overcurrent 11
5CB0 ...Repeated for Neutral Instantaneous Overcurrent 12
Ground Time Overcurrent (Read/Write Grouped Setting) (6 modules)
5D00 Ground Time Overcurrent 1 Function 0 to 1 --- 1 F102 0 (Disabled)
5D01 Ground Time Overcurrent 1 Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
5D02 Ground Time Overcurrent 1 Input 0 to 1 --- 1 F122 0 (Phasor)
5D03 Ground Time Overcurrent 1 Pickup 0 to 30 pu 0.001 F001 1000
5D04 Ground Time Overcurrent 1 Curve 0 to 16 --- 1 F103 0 (IEEE Mod Inv)
5D05 Ground Time Overcurrent 1 Multiplier 0 to 600 --- 0.01 F001 100
5D06 Ground Time Overcurrent 1 Reset 0 to 1 --- 1 F104 0 (Instantaneous)
5D07 Ground Time Overcurrent 1 Block 0 to 65535 --- 1 F300 0
5D08 Ground Time Overcurrent 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
5D09 Ground Time Overcurrent 1 Events 0 to 1 --- 1 F102 0 (Disabled)
5D0A Reserved (6 items) 0 to 1 --- 1 F001 0
5D10 ...Repeated for Ground Time Overcurrent 2
5D20 ...Repeated for Ground Time Overcurrent 3
5D30 ...Repeated for Ground Time Overcurrent 4
5D40 ...Repeated for Ground Time Overcurrent 5
5D50 ...Repeated for Ground Time Overcurrent 6
Ground Instantaneous Overcurrent (Read/Write Grouped Setting) (12 modules)
5E00 Ground Instantaneous Overcurrent 1 Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
5E01 Ground Instantaneous Overcurrent 1 Function 0 to 1 --- 1 F102 0 (Disabled)
5E02 Ground Instantaneous Overcurrent 1 Pickup 0 to 30 pu 0.001 F001 1000
5E03 Ground Instantaneous Overcurrent 1 Delay 0 to 600 s 0.01 F001 0
5E04 Ground Instantaneous Overcurrent 1 Reset Delay 0 to 600 s 0.01 F001 0
5E05 Ground Instantaneous Overcurrent 1 Block 0 to 65535 --- 1 F300 0
5E06 Ground Instantaneous Overcurrent 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
5E07 Ground Instantaneous Overcurrent 1 Events 0 to 1 --- 1 F102 0 (Disabled)
5E08 Reserved (8 items) 0 to 1 --- 1 F001 0
5E10 ...Repeated for Ground Instantaneous Overcurrent 2
5E20 ...Repeated for Ground Instantaneous Overcurrent 3
5E30 ...Repeated for Ground Instantaneous Overcurrent 4
5E40 ...Repeated for Ground Instantaneous Overcurrent 5
5E50 ...Repeated for Ground Instantaneous Overcurrent 6
5E60 ...Repeated for Ground Instantaneous Overcurrent 7
Table B–10: MODBUS MEMORY MAP (Sheet 27 of 65)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT