B-38 T60 Transformer Protection System GE Multilin
B.4 MEMORY MAPPING APPENDIX B
B
65CD Power Swing Detect Delay 2 Pickup 0 to 65.535 s 0.001 F001 17
65CE Power Swing Detect Delay 3 Pickup 0 to 65.535 s 0.001 F001 9
65CF Power Swing Detect Delay 4 Pickup 0 to 65.535 s 0.001 F001 17
65D0 Power Swing Detect Seal In Delay 0 to 65.535 s 0.001 F001 400
65D1 Power Swing Detect Trip Mode 0 to 1 --- 1 F514 0 (Delayed)
65D2 Power Swing Detect Block 0 to 65535 --- 1 F300 0
65D3 Power Swing Detect Target 0 to 2 --- 1 F109 0 (Self-reset)
65D4 Power Swing Detect Event 0 to 1 --- 1 F102 0 (Disabled)
65D5 Power Swing Detect Shape 0 to 1 --- 1 F085 0 (Mho Shape)
65D6 Power Swing Detect Quad Forward Middle 0.1 to 500 ohms 0.01 F001 6000
65D7 Power Swing Detect Quad Forward Outer 0.1 to 500 ohms 0.01 F001 7000
65D8 Power Swing Detect Quad Reverse Middle 0.1 to 500 ohms 0.01 F001 6000
65D9 Power Swing Detect Quad Reverse Outer 0.1 to 500 ohms 0.01 F001 7000
65DA Power Swing Detect Outer Right Blinder 0.1 to 500 ohms 0.01 F001 10000
65DB Power Swing Detect Outer Left Blinder 0.1 to 500 ohms 0.01 F001 10000
65DC Power Swing Detect Middle Right Blinder 0.1 to 500 ohms 0.01 F001 10000
65DD Power Swing Detect Middle Left Blinder 0.1 to 500 ohms 0.01 F001 10000
65DE Power Swing Detect Inner Right Blinder 0.1 to 500 ohms 0.01 F001 10000
65DF Power Swing Detect Inner Left Blinder 0.1 to 500 ohms 0.01 F001 10000
Load Encroachment (Read/Write Grouped Setting)
6700 Load Encroachment Function 0 to 1 --- 1 F102 0 (Disabled)
6701 Load Encroachment Source 0 to 5 --- 1 F167 0 (SRC 1)
6702 Load Encroachment Minimum Voltage 0 to 3 pu 0.001 F001 250
6703 Load Encroachment Reach 0.02 to 250 ohms 0.01 F001 100
6704 Load Encroachment Angle 5 to 50 degrees 1 F001 30
6705 Load Encroachment Pickup Delay 0 to 65.535 s 0.001 F001 0
6706 Load Encroachment Reset Delay 0 to 65.535 s 0.001 F001 0
6707 Load Encroachment Block 0 to 65535 --- 1 F300 0
6708 Load Encroachment Target 0 to 2 --- 1 F109 0 (Self-reset)
6709 Load Encroachment Events 0 to 1 --- 1 F102 0 (Disabled)
670A Reserved (6 items) 0 to 65535 --- 1 F001 0
Phase Undervoltage (Read/Write Grouped Setting) (3 modules)
7000 Phase Undervoltage 1 Function 0 to 1 --- 1 F102 0 (Disabled)
7001 Phase Undervoltage 1 Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
7002 Phase Undervoltage 1 Pickup 0 to 3 pu 0.001 F001 1000
7003 Phase Undervoltage 1 Curve 0 to 1 --- 1 F111 0 (Definite Time)
7004 Phase Undervoltage 1 Delay 0 to 600 s 0.01 F001 100
7005 Phase Undervoltage 1 Minimum Voltage 0 to 3 pu 0.001 F001 100
7006 Phase Undervoltage 1 Block 0 to 65535 --- 1 F300 0
7007 Phase Undervoltage 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
7008 Phase Undervoltage 1 Events 0 to 1 --- 1 F102 0 (Disabled)
7009 Phase Undervoltage 1 Measurement Mode 0 to 1 --- 1 F186 0 (Phase to Ground)
700A Reserved (6 items) 0 to 1 --- 1 F001 0
7013 ...Repeated for Phase Undervoltage 2
7020 ...Repeated for Phase Undervoltage 3
Phase Overvoltage (Read/Write Grouped Setting)
7040 Phase Overvoltage 1 Function 0 to 1 --- 1 F102 0 (Disabled)
7041 Phase Overvoltage 1 Source 0 to 5 --- 1 F167 0 (SRC 1)
7042 Phase Overvoltage 1 Pickup 0 to 3 pu 0.001 F001 1000
7043 Phase Overvoltage 1 Delay 0 to 600 s 0.01 F001 100
7044 Phase Overvoltage 1 Reset Delay 0 to 600 s 0.01 F001 100
7045 Phase Overvoltage 1 Block 0 to 65535 --- 1 F300 0
7046 Phase Overvoltage 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
7047 Phase Overvoltage 1 Events 0 to 1 --- 1 F102 0 (Disabled)
Table B–10: MODBUS MEMORY MAP (Sheet 30 of 65)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT

Table of Contents