GE Multilin T60 Transformer Protection System B-39
APPENDIX B B.4 MEMORY MAPPING
B
7048 Reserved (8 items) 0 to 1 --- 1 F001 0
Distance (Read/Write Grouped Setting)
7060 Distance Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
7061 Memory Duration 5 to 25 cycles 1 F001 10
7062 Force Self-Polarization 0 to 65535 --- 1 F300 0
7063 Force Memory Polarization 0 to 65535 --- 1 F300 0
Phase Distance (Read/Write Grouped Setting (3 modules)
7070 Phase Distance Zone 1 Function 0 to 1 --- 1 F102 0 (Disabled)
7071 Phase Distance Zone 1 Current Supervision 0.05 to 30 pu 0.001 F001 200
7072 Phase Distance Zone 1 Reach 0.02 to 500 ohms 0.01 F001 200
7073 Phase Distance Zone 1 Direction 0 to 2 --- 1 F154 0 (Forward)
7074 Phase Distance Zone 1 Comparator Limit 30 to 90 degrees 1 F001 90
7075 Phase Distance Zone 1 Delay 0 to 65.535 s 0.001 F001 0
7076 Phase Distance Zone 1 Block 0 to 65535 --- 1 F300 0
7077 Phase Distance Zone 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
7078 Phase Distance Zone 1 Events 0 to 1 --- 1 F102 0 (Disabled)
7079 Phase Distance Zone 1 Shape 0 to 1 --- 1 F120 0 (Mho)
Fixed in G60
707A Phase Distance Zone 1 RCA 30 to 90 degrees 1 F001 85
707B Phase Distance Zone 1 DIR RCA 30 to 90 degrees 1 F001 85
707C Phase Distance Zone 1 DIR Comp Limit 30 to 90 degrees 1 F001 90
707D Phase Distance Zone 1 Quad Right Blinder 0.02 to 500 ohms 0.01 F001 1000
707E Phase Distance Zone 1 Quad Right Blinder RCA 60 to 90 degrees 1 F001 85
707F Phase Distance Zone 1 Quad Left Blinder 0.02 to 500 ohms 0.01 F001 1000
7080 Phase Distance Zone 1 Quad Left Blinder RCA 60 to 90 degrees 1 F001 85
7081 Phase Distance Zone 1 Volt Limit 0 to 5 pu 0.001 F001 0
7082 Phase Distance Zone 1 Transformer Voltage Connection 0 to 12 --- 1 F153 0 (None)
7083 Phase Distance Zone 1 Transformer Current Connection 0 to 12 --- 1 F153 0 (None)
7084 Phase Distance Zone 1 Rev Reach 0.02 to 500 ohms 0.01 F001 200
7085 Phase Distance Zone 1 Rev Reach RCA 30 to 90 degrees 1 F001 85
7086 Reserved (10 items) --- --- --- F001 0
7090 ...Repeated for Phase Distance Zone 2
70B0 ...Repeated for Phase Distance Zone 3
Ground Distance (Read/Write Grouped Setting) (3 modules)
7130 Ground Distance Zone 1 Function 0 to 1 --- 1 F102 0 (Disabled)
7131 Ground Distance Zone 1 Current Supervision 0.05 to 30 pu 0.001 F001 200
7132 Ground Distance Zone 1 Reach 0.02 to 500 ohms 0.01 F001 200
7133 Ground Distance Zone 1 Direction 0 to 2 --- 1 F154 0 (Forward)
7134 Ground Distance Zone 1 Comparator Limit 30 to 90 degrees 1 F001 90
7135 Ground Distance Zone 1 Delay 0 to 65.535 s 0.001 F001 0
7136 Ground Distance Zone 1 Block 0 to 65535 --- 1 F300 0
7137 Ground Distance Zone 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
7138 Ground Distance Zone 1 Events 0 to 1 --- 1 F102 0 (Disabled)
7139 Ground Distance Zone 1 Shape 0 to 1 --- 1 F120 0 (Mho)
713A Ground Distance Zone 1 Z0 Z1 Magnitude 0 to 10 --- 0.01 F001 270
713B Ground Distance Zone 1 Z0 Z1 Angle -90 to 90 degrees 1 F002 0
713C Ground Distance Zone 1 RCA 30 to 90 degrees 1 F001 85
713D Ground Distance Zone 1 DIR RCA 30 to 90 degrees 1 F001 85
713E Ground Distance Zone 1 DIR Comp Limit 30 to 90 degrees 1 F001 90
713F Ground Distance Zone 1 Quad Right Blinder 0.02 to 500 ohms 0.01 F001 1000
7140 Ground Distance Zone 1 Quad Right Blinder RCA 60 to 90 degrees 1 F001 85
7141 Ground Distance Zone 1 Quad Left Blinder 0.02 to 500 ohms 0.01 F001 1000
7142 Ground Distance Zone 1 Quad Left Blinder RCA 60 to 90 degrees 1 F001 85
7143 Ground Distance Zone 1 Z0M Z1 Magnitude 0 to 7 --- 0.01 F001 0
Table B–10: MODBUS MEMORY MAP (Sheet 31 of 65)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT