B-40 T60 Transformer Protection System GE Multilin
B.4 MEMORY MAPPING APPENDIX B
B
7144 Ground Distance Zone 1 Z0M Z1 Angle -90 to 90 degrees 1 F002 0
7145 Ground Distance Zone 1 Voltage Level 0 to 5 pu 0.001 F001 0
7146 Ground Distance Zone 1 Non-Homogeneous Angle -40 to 40 degrees 0.1 F002 0
7147 Ground Distance Zone 1 POL Current 0 to 1 --- 1 F521 0 (Zero-seq)
7148 Ground Distance Zone 1 Reverse Reach 0.02 to 500 ohms 0.01 F001 200
7149 Ground Distance Zone 1 Reverse Reach RCA 30 to 90 degrees 1 F001 85
714A Reserved (7 items) 0 to 65535 --- 1 F001 0
7151 ...Repeated for Ground Distance Zone 2
7172 ...Repeated for Ground Distance Zone 3
Phase Directional Overcurrent (Read/Write Grouped Setting)
7260 Phase Directional Overcurrent 1 Function 0 to 1 --- 1 F102 0 (Disabled)
7261 Phase Directional Overcurrent 1 Source 0 to 5 --- 1 F167 0 (SRC 1)
7262 Phase Directional Overcurrent 1 Block 0 to 65535 --- 1 F300 0
7263 Phase Directional Overcurrent 1 ECA 0 to 359 degrees 1 F001 30
7264 Phase Directional Overcurrent 1 Pol V Threshold 0 to 3 pu 0.001 F001 700
7265 Phase Directional Overcurrent 1 Block Overcurrent 0 to 1 --- 1 F126 0 (No)
7266 Phase Directional Overcurrent 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
7267 Phase Directional Overcurrent 1 Events 0 to 1 --- 1 F102 0 (Disabled)
7268 Reserved (8 items) 0 to 1 --- 1 F001 0
Neutral Directional Overcurrent (Read/Write Grouped Setting)
7280 Neutral Directional Overcurrent 1 Function 0 to 1 --- 1 F102 0 (Disabled)
7281 Neutral Directional Overcurrent 1 Source 0 to 5 --- 1 F167 0 (SRC 1)
7282 Neutral Directional Overcurrent 1 Polarizing 0 to 2 --- 1 F230 0 (Voltage)
7283 Neutral Directional Overcurrent 1 Forward ECA -90 to 90 ° Lag 1 F002 75
7284 Neutral Directional Overcurrent 1 Forward Limit Angle 40 to 90 degrees 1 F001 90
7285 Neutral Directional Overcurrent 1 Forward Pickup 0.006 to 30 pu 0.001 F001 50
7286 Neutral Directional Overcurrent 1 Reverse Limit Angle 40 to 90 degrees 1 F001 90
7287 Neutral Directional Overcurrent 1 Reverse Pickup 0.006 to 30 pu 0.001 F001 50
7288 Neutral Directional Overcurrent 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
7289 Neutral Directional Overcurrent 1 Block 0 to 65535 --- 1 F300 0
728A Neutral Directional Overcurrent 1 Events 0 to 1 --- 1 F102 0 (Disabled)
728B Neutral Directional Overcurrent 1 Polarizing Voltage 0 to 1 --- 1 F231 0 (Calculated V0)
728C Neutral Directional Overcurrent 1 Op Current 0 to 1 --- 1 F196 0 (Calculated 3I0)
728D Neutral Directional Overcurrent 1 Offset 0 to 250 ohms 0.01 F001 0
728E Neutral Directional Overcurrent 1 Pos Seq Restraint 0 to 0.5 --- 0.001 F001 63
728F Reserved 0 to 1 --- 1 F001 0
Breaker Arcing Current Settings (Read/Write Setting) (4 modules)
72C0 Breaker 1 Arcing Current Function 0 to 1 --- 1 F102 0 (Disabled)
72C1 Breaker 1 Arcing Current Source 0 to 5 --- 1 F167 0 (SRC 1)
72C2 Breaker 1 Arcing Current Initiate A 0 to 65535 --- 1 F300 0
72C3 Breaker 1 Arcing Current Initiate B 0 to 65535 --- 1 F300 0
72C4 Breaker 1 Arcing Current Initiate C 0 to 65535 --- 1 F300 0
72C5 Breaker 1 Arcing Current Delay 0 to 65.535 s 0.001 F001 0
72C6 Breaker 1 Arcing Current Limit 0 to 50000 kA
2
-cyc 1 F001 1000
72C7 Breaker 1 Arcing Current Block 0 to 65535 --- 1 F300 0
72C8 Breaker 1 Arcing Current Target 0 to 2 --- 1 F109 0 (Self-reset)
72C9 Breaker 1 Arcing Current Events 0 to 1 --- 1 F102 0 (Disabled)
72CA ...Repeated for Breaker 2 Arcing Current
72D4 ...Repeated for Breaker 3 Arcing Current
72DE ...Repeated for Breaker 4 Arcing Current
DCmA Inputs (Read/Write Setting) (24 modules)
7300 DCmA Inputs 1 Function 0 to 1 --- 1 F102 0 (Disabled)
7301 DCmA Inputs 1 ID --- --- --- F205 “DCmA Ip 1"
7307 Reserved 1 (4 items) 0 to 65535 --- 1 F001 0
Table B–10: MODBUS MEMORY MAP (Sheet 32 of 65)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT