B-42 T60 Transformer Protection System GE Multilin
B.4 MEMORY MAPPING APPENDIX B
B
75FD ...Repeated for Disconnect Switch 10
7612 ...Repeated for Disconnect Switch 11
7627 ...Repeated for Disconnect Switch 12
763C ...Repeated for Disconnect Switch 13
7651 ...Repeated for Disconnect Switch 14
7666 ...Repeated for Disconnect Switch 15
767B ...Repeated for Disconnect Switch 16
7690 ...Repeated for Disconnect Switch 17
76A5 ...Repeated for Disconnect Switch 18
76BA ...Repeated for Disconnect Switch 19
76CF ...Repeated for Disconnect Switch 20
76E4 ...Repeated for Disconnect Switch 21
76F9 ...Repeated for Disconnect Switch 22
770E ...Repeated for Disconnect Switch 23
7723 ...Repeated for Disconnect Switch 24
Thermal Overload Protection (Read/Write Settings) (2 modules)
7738 Thermal Protection 1 Function 0 to 1 --- 1 F102 0 (Disabled)
7739 Thermal Protection 1 Source 0 to 5 --- 1 F167 0 (SRC 1)
773A Thermal Protection 1 Base Current 0.2 to 3 pu 0.01 F001 80
773B Thermal Protection 1 K Factor 1 to 1.2 --- 0.05 F001 110
773C Thermal Protection 1 Trip Time Constant 0 to 1000 min. 1 F001 45
773D Thermal Protection 1 Reset Time Constant 0 to 1000 min. 1 F001 45
773E Thermal Protection 1 Minimum Reset Time 0 to 1000 min. 1 F001 20
773F Thermal Protection 1 Reset 0 to 65535 --- 1 F300 0
7740 Thermal Protection 1 Block 0 to 65535 --- 1 F300 0
7741 Thermal Protection 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
7742 Thermal Protection 1 Events 0 to 1 --- 1 F102 0 (Disabled)
7743 Reserved (2 items) --- --- --- F001 0
7745 Repeated for Thermal Protection 2
Ohm Inputs (Read/Write Setting) (2 modules)
7840 Ohm Inputs 1 Function 0 to 1 --- 1 F102 0 (Disabled)
7841 Ohm Inputs 1 ID --- --- --- F205 "Ohm Ip 1 "
7847 Ohm Inputs 1 Reserved (9 items) 0 to 65535 --- 1 F001 0
7850 ...Repeated for Ohm Inputs 2
Phasor Measurement Unit Power Trigger (Read/Write Setting)
7860 PMU 1 Power Trigger Function 0 to 1 --- 1 F102 0 (Disabled)
7861 PMU 1 Power Trigger Active 0.25 to 3 pu 0.001 F001 1250
7862 PMU 1 Power Trigger Reactive 0.25 to 3 pu 0.001 F001 1250
7863 PMU 1 Power Trigger Apparent 0.25 to 3 pu 0.001 F001 1250
7864 PMU 1 Power Trigger Pickup Time 0 to 600 s 0.01 F001 10
7865 PMU 1 Power Trigger Dropout Time 0 to 600 s 0.01 F001 100
7866 PMU 1 Power Trigger Block (3 items) 0 to 65535 --- 1 F300 0
7869 PMU 1 Power Trigger Target 0 to 2 --- 1 F109 0 (Self-reset)
786A PMU 1 Power Trigger Events 0 to 1 --- 1 F102 0 (Disabled)
Phasor Measurement Unit Voltage Trigger (Read/Write Setting)
788C PMU 1 Voltage Trigger Function 0 to 1 --- 1 F102 0 (Disabled)
788D PMU 1 Voltage Trigger Low Voltage 0.25 to 1.25 pu 0.001 F001 800
788E PMU 1 Voltage Trigger High Voltage 0.75 to 1.75 pu 0.001 F001 1200
788F PMU 1 Voltage Trigger Pickup Time 0 to 600 s 0.01 F001 10
7890 PMU 1 Voltage Trigger Dropout Time 0 to 600 s 0.01 F001 100
7891 PMU 1 Voltage Trigger Block (3 items) 0 to 65535 --- 1 F300 0
7894 PMU 1 Voltage Trigger Target 0 to 2 --- 1 F109 0 (Self-reset)
7895 PMU 1 Voltage Trigger Events 0 to 1 --- 1 F102 0 (Disabled)
Table B–10: MODBUS MEMORY MAP (Sheet 34 of 65)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT