GE Multilin T60 Transformer Protection System B-43
APPENDIX B B.4 MEMORY MAPPING
B
Phasor Measurement Unit One-shot Command (Read/Write Setting)
78B4 PMU One-shot Function 0 to 1 --- 1 F102 0 (Disabled)
78B5 PMU One-shot Sequence Number 0 to 59 --- 1 F001 1
78B6 PMU One-shot Time 0 to 235959 --- 1 F050 0
Phasor Measurement Unit Test Values (Read/Write Setting)
78B8 PMU 1 Test Function 0 to 1 --- 1 F102 0 (Disabled)
78B9 PMU 1 Phase A Voltage Test Magnitude 0 to 700 kV 0.01 F003 50000
78BB PMU 1 Phase A Voltage Test Angle -180 to 180 ° 0.05 F002 0
78BC PMU 1 Phase B Voltage Test Magnitude 0 to 700 kV 0.01 F003 50000
78BE PMU 1 Phase B Voltage Test Angle -180 to 180 ° 0.05 F002 -12000
78BF PMU 1 Phase C Voltage Test Magnitude 0 to 700 kV 0.01 F003 50000
78C1 PMU 1 Phase C Voltage Test Angle -180 to 180 ° 0.05 F002 12000
78C2 PMU 1 Auxiliary Voltage Test Magnitude 0 to 700 kV 0.01 F003 50000
78C4 PMU 1 Auxiliary Voltage Test Angle -180 to 180 ° 0.05 F002 0
78C5 PMU 1 Phase A Current Test Magnitude 0 to 9.999 kA 0.001 F004 1000
78C7 PMU 1 Phase A Current Test Angle -180 to 180 ° 0.05 F002 -1000
78C8 PMU 1 Phase B Current Test Magnitude 0 to 9.999 kA 0.001 F004 1000
78CA PMU 1 Phase B Current Test Angle -180 to 180 ° 0.05 F002 -13000
78CB PMU 1 Phase C Current Test Magnitude 0 to 9.999 kA 0.001 F003 1000
78CD PMU 1 Phase C Current Test Angle -180 to 180 ° 0.05 F002 11000
78CE PMU 1 Ground Current Test Magnitude 0 to 9.999 kA 0.001 F004 0
78D0 PMU 1 Ground Current Test Angle -180 to 180 ° 0.05 F002 0
78D1 PMU 1 Test Frequency 20 to 70 Hz 0.001 F003 60000
78D3 PMU 1 Test df/dt -10 to 10 Hz/s 0.001 F002 0
Phasor Measurement Unit Recorder Configuration Counter Command (Read/Write Command)
7928 PMU 1 Recorder Clear Configuration Counter 0 to 1 --- 1 F126 0 (No)
Phasor Measurement Unit Recording Values (Read Only)
792C PMU 1 Available Records 0 to 65535 --- 1 F001 0
792D PMU 1 Second Per Record 0 to 6553.5 --- 0.1 F003 0
792F PMU 1 Last Cleared Date 0 to 400000000 --- 1 F050 0
Phasor Measurement Unit Network Reporting Configuration (Read/Write Setting)
7940 PMU Network Reporting Function 0 to 1 --- 1 F102 0 (Disabled)
7941 PMU Network Reporting ID Code 1 to 65534 --- 1 F001 1
7942 PMU Network Reporting Rate 0 to 11 --- 1 F544 3 (5/sec.)
7943 PMU Network Reporting Style 0 to 1 --- 1 F546 0 (Polar)
7944 PMU Network Reporting Format 0 to 1 --- 1 F547 0 (Integer)
7945 PMU Network PDC Control 0 to 1 --- 1 F102 0 (Disabled)
7946 PMU TCP Port Number 1 to 65535 --- 1 F001 4712
7947 PMU UDP Port Number 1 1 to 65535 --- 1 F001 4713
7948 PMU UDP Port Number 2 1 to 65535 --- 1 F001 4714
Phasor Measurement Unit Basic Configuration (Read/Write Setting)
7949 PMU 1 Function 0 to 1 --- 1 F102 0 (Disabled)
794A PMU 1 IDcode 1 to 65534 --- 1 F001 1
794B PMU 1 STN --- --- --- F203 “GE-UR-PMU”
7953 PMU 1 Source 0 to 5 --- 1 F167 0 (SRC 1)
7954 PMU 1 Post-Filter 0 to 5 --- 1 F540 1 (Symm-3-point)
Phasor Measurement Unit Calibration (Read/Write Setting)
7979 PMU 1 Va Calibration Angle -5 to 5 ° 0.05 F002 0
797A PMU 1 Vb Calibration Angle -5 to 5 ° 0.05 F002 0
797B PMU 1 Vc Calibration Angle -5 to 5 ° 0.05 F002 0
797C PMU 1 Vx Calibration Angle -5 to 5 ° 0.05 F002 0
797D PMU 1 Ia Calibration Angle -5 to 5 ° 0.05 F002 0
797E PMU 1 Ib Calibration Angle -5 to 5 ° 0.05 F002 0
797F PMU 1 Ic Calibration Angle -5 to 5 ° 0.05 F002 0
Table B–10: MODBUS MEMORY MAP (Sheet 35 of 65)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT