B-52 T60 Transformer Protection System GE Multilin
B.4 MEMORY MAPPING APPENDIX B
B
9A0F FlexElement™ 8 Actual
-2147483.647 to 2147483.647
--- 0.001 F004 0
9A11 FlexElement™ 9 Actual
-2147483.647 to 2147483.647
--- 0.001 F004 0
9A13 FlexElement™ 10 Actual
-2147483.647 to 2147483.647
--- 0.001 F004 0
9A15 FlexElement™ 11 Actual
-2147483.647 to 2147483.647
--- 0.001 F004 0
9A17 FlexElement™ 12 Actual
-2147483.647 to 2147483.647
--- 0.001 F004 0
9A19 FlexElement™ 13 Actual
-2147483.647 to 2147483.647
--- 0.001 F004 0
9A1B FlexElement™ 14 Actual
-2147483.647 to 2147483.647
--- 0.001 F004 0
9A1D FlexElement™ 15 Actual
-2147483.647 to 2147483.647
--- 0.001 F004 0
9A1F FlexElement™ 16 Actual
-2147483.647 to 2147483.647
--- 0.001 F004 0
Breaker Restrike (Read/Write Settings) (3 modules)
9AD9 Breaker Restrike 1 Function 0 to 1 --- 1 F102 0 (Disabled)
9ADA Breaker Restrike 1 Block 0 to 65535 --- 1 F300 0
9ADB Breaker Restrike 1 Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
9ADC Breaker Restrike 1 Pickup 0.10 to 2.00 pu 0.01 F001 50
9ADD Breaker Restrike 1 Reset Delay 0 to 65.535 s 0.001 F001 100
9ADE Breaker Restrike 1 HF Detect 0 to 1 --- 1 F102 1 (Enabled)
9ADF Breaker Restrike 1 Breaker Open 0 to 65535 --- 1 F300 0
9AE0 Breaker Restrike 1 Open Command 0 to 65535 --- 1 F300 0
9AE1 Breaker Restrike 1 Close Command 0 to 65535 --- 1 F300 0
9AE2 Breaker Restrike 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
9AE3 Breaker Restrike 1 Events 0 to 1 --- 1 F102 0 (Disabled)
9AE4 Reserved (2 items) --- --- --- F002 0
9AE6 ...Repeated for Breaker Restrike 2
9AF3 ...Repeated for Breaker Restrike 3
Teleprotection Inputs/Outputs (Read/Write Settings)
9B00 Teleprotection Function 0 to 1 --- 1 F102 0 (Disabled)
9B01 Teleprotection Number of Terminals 2 to 3 --- 1 F001 2
9B02 Teleprotection Number of Channels 1 to 2 --- 1 F001 1
9B03 Teleprotection Local Relay ID 0 to 255 --- 1 F001 0
9B04 Teleprotection Terminal 1 ID 0 to 255 --- 1 F001 0
9B05 Teleprotection Terminal 2 ID 0 to 255 --- 1 F001 0
9B06 Reserved (10 items) 0 to 1 --- 1 F001 0
9B10 Teleprotection Input 1-n Default States (16 items) 0 to 3 --- 1 F086 0 (Off)
9B30 Teleprotection Input 2-n Default States (16 items) 0 to 3 --- 1 F086 0 (Off)
9B50 Teleprotection Output 1-n Operand (16 items) 0 to 65535 --- 1 F300 0
9B70 Teleprotection Output 2-n Operand (16 items) 0 to 65535 --- 1 F300 0
Teleprotection Inputs/Outputs Commands (Read/Write Command)
9B90 Teleprotection Clear Lost Packets 0 to 1 --- 1 F126 0 (No)
Teleprotection Channel Tests (Read Only)
9B91 Teleprotection Channel 1 Status 0 to 2 --- 1 F134 1 (OK)
9B92 Teleprotection Channel 1 Number of Lost Packets 0 to 65535 --- 1 F001 0
9B93 Teleprotection Channel 2 Status 0 to 2 --- 1 F134 2 (n/a)
9B94 Teleprotection Channel 2 Number of Lost Packets 0 to 65535 --- 1 F001 0
9B95 Teleprotection Network Status 0 to 2 --- 1 F134 2 (n/a)
9BA0 Teleprotection Channel 1 Input States 0 to 1 --- 1 F500 0
9BA1 Teleprotection Channel 2 Input States 0 to 1 --- 1 F500 0
9BB0 Teleprotection Input 1 States, 1 per register (16 items) 0 to 1 --- 1 F108 0 (Off)
9BC0 Teleprotection Input 2 States, 1 per register (16 items) 0 to 1 --- 1 F108 0 (Off)
VT Fuse Failure (Read/Write Setting) (6 modules)
A040 VT Fuse Failure 1 Function 0 to 1 --- 1 F102 0 (Disabled)
A041 ...Repeated for VT Fuse Failure 2
A042 ...Repeated for VT Fuse Failure 3
A043 ...Repeated for VT Fuse Failure 4
A044 ...Repeated for VT Fuse Failure 5
Table B–10: MODBUS MEMORY MAP (Sheet 44 of 65)