GE Multilin T60 Transformer Protection System B-53
APPENDIX B B.4 MEMORY MAPPING
B
A045 ...Repeated for VT Fuse Failure 6
Pilot Permissive Overreach Transfer Trip (POTT) Settings (Read/Write)
A070 POTT Scheme Function 0 to 1 --- 1 F102 0 (Disabled)
A071 POTT Permissive Echo 0 to 1 --- 1 F102 0 (Disabled)
A072 POTT Rx Pickup Delay 0 to 65.535 s 0.001 F001 0
A073 POTT Transient Block Pickup Delay 0 to 65.535 s 0.001 F001 20
A074 POTT Transient Block Reset Delay 0 to 65.535 s 0.001 F001 90
A075 POTT Echo Duration 0 to 65.535 s 0.001 F001 100
A076 POTT Line End Open Pickup Delay 0 to 65.535 s 0.001 F001 50
A077 POTT Seal In Delay 0 to 65.535 s 0.001 F001 400
A078 POTT Ground Direction OC Forward 0 to 65535 --- 1 F300 0
A079 POTT Rx 0 to 65535 --- 1 F300 0
A07A POTT Echo Lockout 0 to 65.535 s 0.001 F001 250
A07B POTT Target 0 to 2 --- 1 F109 0 (Self-reset)
A07C POTT Events 0 to 1 --- 1 F102 0 (Disabled)
Selector Switch Actual Values (Read Only)
A210 Selector Switch 1 Position 1 to 7 --- 1 F001 0
A211 Selector Switch 2 Position 1 to 7 --- 1 F001 1
Selector Switch Settings (Read/Write) (2 modules)
A280 Selector 1 Function 0 to 1 --- 1 F102 0 (Disabled)
A281 Selector 1 Range 1 to 7 --- 1 F001 7
A282 Selector 1 Timeout 3 to 60 s 0.1 F001 50
A283 Selector 1 Step Up 0 to 65535 --- 1 F300 0
A284 Selector 1 Step Mode 0 to 1 --- 1 F083 0 (Time-out)
A285 Selector 1 Acknowledge 0 to 65535 --- 1 F300 0
A286 Selector 1 Bit0 0 to 65535 --- 1 F300 0
A287 Selector 1 Bit1 0 to 65535 --- 1 F300 0
A288 Selector 1 Bit2 0 to 65535 --- 1 F300 0
A289 Selector 1 Bit Mode 0 to 1 --- 1 F083 0 (Time-out)
A28A Selector 1 Bit Acknowledge 0 to 65535 --- 1 F300 0
A28B Selector 1 Power Up Mode 0 to 2 --- 1 F084 0 (Restore)
A28C Selector 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
A28D Selector 1 Events 0 to 1 --- 1 F102 0 (Disabled)
A28E Reserved (10 items) --- --- 1 F001 0
A298 ...Repeated for Selector 2
DNP/IEC Points (Read/Write Setting)
A300 DNP/IEC 60870-5-104 Binary Input Points (256 items) 0 to 65535 --- 1 F300 0
A400 DNP/IEC 60870-5-104 Analog Input Points (256 items) 0 to 65535 --- 1 F600 0
Volts Per Hertz (Read/Write Grouped Setting) (2 modules)
A580 Volts Per Hertz 1 Function 0 to 1 --- 1 F102 0 (Disabled)
A581 Volts Per Hertz 1 Source 0 to 5 --- 1 F167 0 (SRC 1)
A582 Volts Per Hertz 1 Pickup 0.8 to 4 pu 0.01 F001 80
A583 Volts Per Hertz 1 Curves 0 to 7 --- 1 F240 0 (Definite Time)
A584 Volts Per Hertz 1 TD Multiplier 0.05 to 600 --- 0.01 F001 100
A585 Volts Per Hertz 1 Block 0 to 65535 --- 1 F300 0
A586 Volts Per Hertz 1 Events 0 to 1 --- 1 F102 0 (Disabled)
A587 Volts Per Hertz 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
A588 Volts Per Hertz 1 T Reset 0 to 1000 s 0.1 F001 10
A589 Volts Per Hertz 1 Voltage Mode 0 to 1 --- 1 F186 0 (Phase-to-Ground)
A58A ...Repeated for Volts Per Hertz 2
Volts Per Hertz Actual Values (Read Only) (2 modules)
A5A0 Volts Per Hertz 1 0 to 65.535 pu 0.001 F001 0
A5A1 Volts Per Hertz 2 0 to 65.535 pu 0.001 F001 0
Table B–10: MODBUS MEMORY MAP (Sheet 45 of 65)