B-54 T60 Transformer Protection System GE Multilin
B.4 MEMORY MAPPING APPENDIX B
B
FlexCurves C and D (Read/Write Setting)
A600 FlexCurve C (120 items) 0 to 65535 ms 1 F011 0
A680 FlexCurve D (120 items) 0 to 65535 ms 1 F011 0
Non Volatile Latches (Read/Write Setting) (16 modules)
A700 Non-Volatile Latch 1 Function 0 to 1 --- 1 F102 0 (Disabled)
A701 Non-Volatile Latch 1 Type 0 to 1 --- 1 F519 0 (Reset Dominant)
A702 Non-Volatile Latch 1 Set 0 to 65535 --- 1 F300 0
A703 Non-Volatile Latch 1 Reset 0 to 65535 --- 1 F300 0
A704 Non-Volatile Latch 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
A705 Non-Volatile Latch 1 Events 0 to 1 --- 1 F102 0 (Disabled)
A706 Reserved (4 items) --- --- --- F001 0
A70A ...Repeated for Non-Volatile Latch 2
A714 ...Repeated for Non-Volatile Latch 3
A71E ...Repeated for Non-Volatile Latch 4
A728 ...Repeated for Non-Volatile Latch 5
A732 ...Repeated for Non-Volatile Latch 6
A73C ...Repeated for Non-Volatile Latch 7
A746 ...Repeated for Non-Volatile Latch 8
A750 ...Repeated for Non-Volatile Latch 9
A75A ...Repeated for Non-Volatile Latch 10
A764 ...Repeated for Non-Volatile Latch 11
A76E ...Repeated for Non-Volatile Latch 12
A778 ...Repeated for Non-Volatile Latch 13
A782 ...Repeated for Non-Volatile Latch 14
A78C ...Repeated for Non-Volatile Latch 15
A796 ...Repeated for Non-Volatile Latch 16
Digital Counter (Read/Write Setting) (8 modules)
A800 Digital Counter 1 Function 0 to 1 --- 1 F102 0 (Disabled)
A801 Digital Counter 1 Name --- --- --- F205 “Counter 1"
A807 Digital Counter 1 Units --- --- --- F206 (none)
A80A Digital Counter 1 Block 0 to 65535 --- 1 F300 0
A80B Digital Counter 1 Up 0 to 65535 --- 1 F300 0
A80C Digital Counter 1 Down 0 to 65535 --- 1 F300 0
A80D Digital Counter 1 Preset –2147483647 to
2147483647
--- 1 F004 0
A80F Digital Counter 1 Compare –2147483647 to
2147483647
--- 1 F004 0
A811 Digital Counter 1 Reset 0 to 65535 --- 1 F300 0
A812 Digital Counter 1 Freeze/Reset 0 to 65535 --- 1 F300 0
A813 Digital Counter 1 Freeze/Count 0 to 65535 --- 1 F300 0
A814 Digital Counter 1 Set To Preset 0 to 65535 --- 1 F300 0
A815 Reserved (11 items) --- --- --- F001 0
A820 ...Repeated for Digital Counter 2
A840 ...Repeated for Digital Counter 3
A860 ...Repeated for Digital Counter 4
A880 ...Repeated for Digital Counter 5
A8A0 ...Repeated for Digital Counter 6
A8C0 ...Repeated for Digital Counter 7
A8E0 ...Repeated for Digital Counter 8
Restricted Ground Fault (Read/Write Grouped Setting) (6 modules)
A960 Restricted Ground Fault 1 Function 0 to 1 --- 1 F102 0 (Disabled)
A961 Restricted Ground Fault 1 Source 0 to 5 --- 1 F167 0 (SRC 1)
A962 Restricted Ground Fault 1 Pickup 0.005 to 30 pu 0.001 F001 80
A963 Restricted Ground Fault 1 Slope 0 to 100 % 1 F001 40
A964 Restricted Ground Fault 1 Delay 0 to 600 s 0.01 F001 0
Table B–10: MODBUS MEMORY MAP (Sheet 46 of 65)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT