4.4 Pipes
Pipesandsystemcomponentsmustbecleananddryinsideandfreeofscale,swarfandlayersof
rustandphosphate.Onlyuseair-tightparts.
Lay pipes correctly. Suitablevibration compensators mustbe providedto preventpipes being
crackedandbrokenbyseverevibrations.
Ensureaproperoilreturn.
Keeppressurelossestoanabsoluteminimum.
The pipe connectionshavegraduatedinsidediameterssothatpipeswith
standartmillimetreandinchdimensionscanbeused.
Theconnectiondiametersoftheshut-offvalvesareratedformaximum
compressoroutput.Theactualrequiredpipecrosssectionmustbe
matched to the output. The same applies for non-return valves.
Fig.10:graduated
internaldiameter
4.3 Pipe connections
ATTENTION Damage possible.
Superheating can damage the valve.
Remove the pipe supports from the valve for soldering.
Only solder using inert gas to inhibit oxidation products (scale).