Terminalbox
Fig.18
ATTENTION
Measure circuit BT1 and BT2
(PTC sensor) must not come
into contact with external
voltage.
This would destroy the trigger
unit INT69 G and PTC sensors.
5.6 Electronic trigger unit INT69 G
5.7 Connection of the trigger unit INT69 G
The compressormotor istted withcold conductortemperaturesensors (PTC)connectedto the
electronictrigger unitINT69G in the terminal box. In case of excess temperature in the motor
winding,theINT69Gdeactivatesthemotorcontactor.Oncecooled,itcanberestartedonlyifthe
electroniclockoftheoutputrelay(terminalsB1+B2)isreleasedbyinterruptingthesupplyvoltage.
Thehotgassideofthecompressorcanalsobeprotectedagainstovertemperatureusingthermal
protectionthermostats(accessory).
The unit trips when an overload or inadmissible operating conditions occur. Find and remedy
the cause.
INFO The relay switching outputis executedas a oating changeover
contact.Thiselectricalcircuitoperatesaccordingtothequiescent
current principle, i.e. the relay drops into a the idle position and
deactivates the motor contactor even in case of a sensor break or
open circuit.
INFO Connect the trigger unit INT69 G in accordance with the circuit dia-
gram. Protect the trigger unit with a delayed-action fuse (FC2) of
max. 4 A. In order to guarantee the protection function, install the
triggerunitastherstelementinthecontrolpowercircuit.
5| Electrical connection