11
The system has stopped because the water temperature in the water heater reached 119 °F
(48 °C).
Warning! Do the following
operations with precaution
the water heater's body
may be very hot.
• Measure the water
temperature with an
DIGITAL thermometer
and compare the
measured temperature
with the one displayed
on the keypad�
HL error message
Troubleshooting
If the measured temperature is below 119 °F (48°C)
and the water heater's body is hot:
• With care, verify the water heater's body temperature�
If it is hot, assure yourself that nothing is blocking the
water flow (closed valves or dirty filter)�
• Turn the spa off and turn it back on to reinitialise the
system�
• If error HL persists replace the water heater�
• If error HL persists replace the control system�
If the measured
temperature is inferior to
119 °F (48 °C):
For the in�yj-re control
systems:
• Verify that the regulation
and overheat probe is
correctly placed in the
plumbing�
If it is, assure yourself
that nothing is blocking
the water flow (closed
valves or clogged filter)�
• Verify that the probe is
correctly plugged into
the probe connector
(P40)�
• Turn the spa off and
turn it back on to
reinitialise the system�
• If error HL persists
replace the probe�
• If error HL persists after
the probe replacement,
replace the control
system�
Probe connector (regulation
and overheat captor)
in.yj-re