EasyManuals Logo

gefran 600 User Manual

gefran 600
31 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #7 background imageLoading...
Page #7 background image
lo.l
of.2
xs.2
l5.2
Minimum limit auxiliary
input scale
Offset correction
of aux input
0.0 ... 999.9
Maximum limit auxiliary
input scale
0.0 ... 999.9
-99.9 ... 99.9
scale points
Lower limit for setting SP
and absolute alarms
Lo.S ... Hi.S
Upper limit for setting SP
and absolute alarms
Lo.S ... Hi.S
• Out
Out
Output settings
Select
reference
signal for
alarm 1
AL.1.r, AL.2.r, AL.3.r
Select
reference
signal for
alarm 2
Select
reference
signal for
alarm 3
AL.x.r Variable to be compared Reference setpoint
0 PV (Process variable) AL
1 SSP (active setpoint) AL (only absolute)
2 PV (process variable) AL (only relative and
referred to SP1 with
multiset function)]
Alarm
type 1
Alarm
type 2
Alarm
type 3
+8 to disable on power up until first interception
+16 to latch alarm
+ 32 Hys becomes delay time when alarm trips (0...999 sec.) (excluding symmetrical absolute)
+ 64 Hys becomes delay time when alarm trips (0...999 min.) (excluding symmetrical absolute)
AL.x.t Direct (high limit) Absolute or Normal
Inverse (low limit) relative to
Symmetrical
active setpoint (window)
0 direct absolute normal
1 inverse absolute normal
2 direct relative normal
3 inverse relative normal
4 direct absolute
symmetrical
5 inverse absolute
symmetrical
6 direct relative
symmetrical
7 inverse relative
symmetrical
AL.1.t, AL.2.t, AL.3.t
HB alarm
function
+ 0 assigned to Out1 (only for Hb_F= 0, 1, 2)
+ 4 assigned to Out2 (only for Hb_F= 0, 1, 2)
+ 12 assigned to Out4 (only for Hb_F= 0, 1, 2)
+16 inverse HB alarm
a1.r
a2.r
a3.r
a1.t
xb.f
a2.t
a3.t
xi.l
Val. Function description
0 Relay, logic output: alarm active
on load current level lower
than setpoint during the
ON time of the control output
1 Relay, logic output: alarm active
on load current level higher
than setpoint during the
OFF time of the control output
2 Alarm active if one of functions 0 and 1
is true (OR logic between 0 and 1) (*)
3 Continuous heat alarm (**)
7 Continuous cool alarm (**)
(*) minimum setting is fixed at 12% of amperometric full scale
(**) As type 0 without reference to cycle time
Notes:
- The HB alarm is disabled if assigned to a rapid output (except codes 3 and 7)
- When the CT input is present, faceplate LED OUT3 always indicates the state of the HB alarm.
780336L_MHW_600_07-2011_ENG
7 / 31

Other manuals for gefran 600

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the gefran 600 and is the answer not in the manual?

gefran 600 Specifications

General IconGeneral
Input TypeThermocouple, RTD, Voltage, Current
Output TypeRelay, SSR, Voltage, Current
Power Supply24V AC/DC, 100-240V AC
Dimensions48x96mm, 96x96mm
CommunicationRS485
Operating Temperature0...+50 °C / 32...+122 °F
Storage Temperature-20...+70 °C / -4...+158 °F
Control TypePID Controller

Related product manuals