App 3-23
5. BACnet Object Properties
This section provides the predetermined configuration of the inverter. User can achieve the
optimizated situation at any necessary modification.
Refer to Table 4.1 for the property information of inverter objects and user can learn the inverter
messages from the inverter objects.
Refer to Table 4.2 ~ Table 4.7 for the related object information that inverter supports. User can
control/ read each object with the application requirements.
Table 4.1 Inverter property list
Property
Inverter
Object_Identifier
DEV
Object_Name
GEFRAN BDI50
Object_Type
8
System_Status
0
Vendor_Name
GEFRAN BDI50
Vendor_ Identifier
461
Model_Name
Gefran spa
Firmware_Revision
0.14
Applocation_Software_Supported
0.14
Protocol_Version
1
Protocol_Revision
5
Protocol_Services_Supported
{ readProperty , writeProperty , who is }
Protocol_Object_Type_Supported
{ Analog_Input , Analog_Output, Analog_Value
Binary_ Input, Binary_Output, Binary_Value,
Device}
Max_Masters
127
Max_Info_Frames
1
Location
Italy